MODEL GMDIO - GRAPHITE SERIES DIGITAL MODULE
GENERAL DESCRIPTION
The Model GMDIO14 module is a digital I/O module designed for use with
the Graphite Series. This module offers eight inputs and six outputs that can be
used to monitor contact or sensor inputs and actuate relays, solenoids, PLC
inputs, etc.
The inputs accept standard DC inputs or contact closures, and are configured
for Sink/Source signals via external switches. Additionally, each input has a
switch selectable input filter that can be used to prevent contact bounce. Each
input may also be software configured as a high-active or low-active input.
The module is available with relay or NFET outputs that are capable of
switching up to one amp each (NFET DC only). For applications requiring large
loads to be controlled, several DIN rail mount relays are available.
The module connects and communicates via proprietary USB connection to the
various Graphite host devices. The Graphite host devices, equipped with serial
ports as well as an Ethernet port(s), allows the system to share data with PCs,
PLCs, and SCADA systems. The maximum number of modules varies for each
Graphite device, see specific models for details.
Once programmed, the module will continue to operate/control independent of
the Graphite host device as long as power is applied. Remove power from the host
device before installing or replacing any modules.
DIMENSIONS In inches (mm)
2.97 (76)
4.65
(118)
 ADDS I/O CAPABILITY TO THE GRAPHITE SERIES
 EIGHT INPUT, SIX OUTPUT DIGITAL MODULE
 INPUTS ISOLATED FROM OUTPUTS
 INPUTS INDEPENDENTLY SWITCH SELECTABLE FOR SINK OR
SOURCE SIGNALS
 INPUTS INDEPENDENTLY CONFIGURABLE FOR HIGH OR LOW
ACTIVE STATE
 INPUTS INDEPENDENTLY SWITCH SELECTABLE FOR HIGH OR
LOW FREQUENCY SIGNALS
 RELAY OR NFET OUTPUT MODELS AVAILABLE
CONFIGURATION
The Graphite Series is configured with Windows
software. The software is an easy to use, graphical interface that provides a
means of communication configuration, as well as commissioning and
calibration of new systems.
SAFETY SUMMARY
All safety related regulations, local codes and instructions that appear in the
manual or on equipment must be observed to ensure personal safety and to
prevent damage to either the instrument or equipment connected to it. If
equipment is used in a manner not specified by the manufacturer, the protection
provided by the equipment may be impaired.
Do not use the module to directly command motors, valves, or other actuators
not equipped with safeguards. To do so can be potentially harmful to persons or
equipment in the event of a fault to the module.
CAUTION: Risk of Danger.
Read complete instructions prior to
installation and operation of the unit.
1.25 (32)
1
Bulletin No. GMDIO-A
Drawing No. LP0921
Effective 07/13
®
®
compatible Crimson
CAUTION: Risk of electric shock.

Advertisement

Table of Contents
loading
Need help?

Need help?

Do you have a question about the GMDIO Series and is the answer not in the manual?

Questions and answers

Summary of Contents for red lion GMDIO Series

  • Page 1 Bulletin No. GMDIO-A Drawing No. LP0921 Effective 07/13 Tel +1 (717) 767-6511 Fax +1 (717) 764-0839 www.redlion.net MODEL GMDIO - GRAPHITE SERIES DIGITAL MODULE  ADDS I/O CAPABILITY TO THE GRAPHITE SERIES  EIGHT INPUT, SIX OUTPUT DIGITAL MODULE  INPUTS ISOLATED FROM OUTPUTS ...
  • Page 2: General Specifications

    GENERAL SPECIFICATIONS 6. ISOLATION LEVEL: 500 Vrms @ 50/60 Hz for 1 minute between the following: 1. POWER: Power will be supplied by the Graphite host device. Inputs 2. LEDs: Outputs STS - Status LED shows module condition. Graphite Host Power Supply Input IN1-IN8 - LEDs are lit when associated input is active.
  • Page 3: Emc Installation Guidelines

    5. In extremely high EMI environments, the use of external EMI suppression Visit RLC’s web site at www.redlion.net for more information on EMI devices such as Ferrite Suppression Cores for signal and control cables is guidelines, Safety and CE issues as they relate to Red Lion Controls products. HARDWARE INPUT SWITCHES Each input is independently configurable for sinking or sourcing signals.
  • Page 4: Hardware Installation

    HARDWARE INSTALLATION Modules must be installed beginning with slot 1 (left-most slot), with no empty slots between the modules, and the order must match the modules order in Crimson. Torque screws to 6.0 pound-force inch (96 ounce-force inch) WARNING: Disconnect all power to the unit before installing or removing modules.
  • Page 5: Firmware Upgrade

    LEDS FIRMWARE UPGRADE The module’s firmware is stored in flash memory so that software/hardware STS – STATUS LED conflicts are avoided, and so features can be added in the future. The Status LED is a green LED that provides information regarding the state During a download, Crimson compares its own library of firmware files with of the module.
  • Page 6 This page intentionally left blank...
  • Page 7 This page intentionally left blank...
  • Page 8 The Company disclaims all liability for any affirmation, promise or representation with respect to the products. The customer agrees to hold Red Lion Controls harmless from, defend, and indemnify RLC against damages, claims, and expenses arising out of subsequent sales of RLC products or products...

This manual is also suitable for:

Graphite seriesGmdio14

Table of Contents