Operating options
6.1.4
Basic settings
Function
Function
group
BASE
UNIT Technical unit
ZERO Zero point
configuration
GETZ Zero point
adoption
DISP
Display
TAU
Damping: display
value, output signal
BASE
DESI
DESINA
6.1.5
Output setting - 1x or 2x switch output
• Hysteresis function
The hysteresis function enables two-point control via a hysteresis. Depending on the
temperature T, the hysteresis can be set via the switch point SP and the switchback point
RSP.
• Window function
The window function allows a process temperature range to be monitored.
• NO contact or NC contact
This switch function is freely selectable.
20
Settings Description
°C
Select unit on display:
°F
°C, °F, K factory setting: °C
K
0.0
Position adjustment:
within ±10 °C/K (18 °F) of the upper sensor limit
0.0
No settings possible (not available in the PC software)
PV
PV: Display measured value
PVR0
PVRO: Display of measured value rotated by 180°
SP
SP: Display set switch point
SPRO
SPRO: Display of set switch point rotated by 180°
OFF
OFF: Display off
OFFR
OFFR: Display off rotated by 180°
Factory setting: current measured value (PV)
0.0
Damping of measured value or display value and output: 0 (no
damping) or 9 to 40 s (in increments of 1 s)
Factory setting: 0 s
NO
The PIN assignment of the M12 connector is in accordance with
YES
the guidelines of DESINA.
Factory setting: NO
DESINA can be selected only if output 1 and 2 are
selected.
Temperature switch OTR31, OTR35