TABLE 36: UNIT CONTROL BOARD FLASH CODES
FLASH CODE
On Steady
This is a Control Failure
1 Flash
Not Applicable
2 Flashes
Control waiting ASCD
3 Flashes
HPS1 Compressor Lockout
4 Flashes
HPS2 Compressor Lockout
5 Flashes
LPS1 Compressor Lockout
6 Flashes
LPS2 Compressor Lockout
7 Flashes
FS1 Compressor Lockout
8 Flashes
FS2 Compressor Lockout
9 Flashes
Ignition Control Locked Out / Ignition Control Failure
10 Flashes
Compressors Locked Out on Low Outdoor Air Temperature
Compressors locked out because the Economizer is using free
11 Flashes
1
Cooling
12 Flashes
Unit Locked Out due to Fan Overload Switch Failure
13 Flashes
Compressor Held Off due to Low Voltage
14 Flashes
EEPROM Storage Failure
OFF
No Power or Control Failure
1.
Non-alarm condition.
Check
Alarm
History
Reset All
ASCDs for
One Cycle
Non Alarm
Condition Green
LED Flashing
Current Alarm
Flashed
Red LED
FIGURE 27 - UNIT CONTROL BOARD
Johnson Controls Unitary Products
DESCRIPTION
1
1
GREEN
RED
LED
LED
16
8
-
-
-
-
Flashing
Off
Off
Off
Off
Off
Off
Off
Off
Off
Off
Off
Off
On
Off
On
1
Flashing
On
Flashing
On
Off
On
Flashing
On
Off
On
Off
Off
284812-YIM-D-1008
RED
RED
RED
LED
LED
LED
4
2
1
-
-
-
-
-
-
Off
On
Off
Off
On
On
On
Off
Off
On
Off
On
On
On
Off
On
On
On
Off
Off
Off
Off
Off
On
Off
On
Off
Off
On
On
On
Off
Off
On
Off
On
On
On
Off
Off
Off
Off
75

Advertisement

Table of Contents
loading

This manual is also suitable for:

Sunline magnum wj180Sunline magnum wj300

Table of Contents