Worked Penetration
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Grease Viscosity, SSU At 100 F (38 C)
Soap Type
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
N–H Bomb, Minimum Hours For 20 PSI (1.4 Bar) Drop
at 210 F (99 C)
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Bleeding, Maximum Weight % In 500 Hours 212 F (100 C)
Rust Inhibiting
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Type of Service
Standard
One– or Two–Shift Operation
Severe
Continuous Operation
Very Severe
Dirty Locations, High
Ambient Temperature
ELECTRIC MOTOR GREASE RECOMMENDATIONS
. . . . . . . . . . . . . . . . . . . . . . . . .
ELECTRIC MOTOR REGREASING INTERVAL
Typical Examples
13–8–606
Standard
Service
265–296
400–550
Lithium
750
. . . . . . . .
10
Yes
Rating
150 HP (112 KW)
Above 150 HP (112 KW)
150 HP (112 KW)
Above 150 HP (112 KW)
150 HP (112 KW)
Above 150 HP (112 KW)
Page 14
High
Temperature
220–240
475–525
Lithium
1000
3
Yes
Relubrication
Interval
18 Months
12 Months
9 Months
6 Months
4 Months
2 Months