6. Operating the air heater

6.1. Burner cycle

The air heater's display shows the current status of the
burner cycle (figure 10).
Figure 10 - Display of the air heater
Display
Status
Description
0
Stand-by
Waiting for heat demand.
1
Reset
Software reset.
3
Pre-check
Zero position check pressure
switch.
4
Pre-purge
30 seconds of pre ventilation
by the combustion fan. The
pressure switch is checked.
5
Pre-ignition
Ignition without opening the
gas valve.
6
Ignition
5 seconds of ignition. The gas
valve opens.
7
Flame check
The air heater checks if the
flame is present.
8
Burn
9
Minimum
Before the flame stops,
the burner will modulate to
minimum power.
10
Burner off
11
Post purge
Burner fan purges with fresh
air.
System fan cools the heat
exchanger.
P
Anti-shuttle
The heater can not generate
a heat demand during this
period.
F
Ventilation
Request to start (summer)
ventilation mode.
12

6.2. Manual operation

1. Press and hold the (+) and (-) buttons for 1 second
to enter the manual mode.
2. Press the (+) or (-) button to select the value of a
system test mode.
3. Press the OK/RESET button to save the system test
mode or press the RETURN button to cancel the
mode selection.
Display
0
6
7
8
Time
(seconds)
-
-

6.3. Minimum firing time

-
The heater will always fire for a minimum of 1 minute, even
30
if the heat demand stops. This is to avoid a large amount of
start and stops.
-
NOTICE
5
and gives an error.
-

6.4. Summer ventilation

> 60
The fan can be set to run in the summer. Follow the
-
instructions in the user manual of the special Room
thermostat.
-

6.5. Overheating protection

60 - 120
The air heater's heat exchanger and flue system are both
protected from excessive temperatures.
-
6.5.1.
-
An NTC sensor is located near (or on) the heat exchanger.
This sensor monitors the heat exchanger temperature.
System test
Description
mode
Requests on
The system is inactive, but accepts RT or
0-10 V input requests.
Requests off
The system is inactive and does not accept
RT or 0-10 V input requests.
12-hour heat The heater burns for 12 hours at a high
power.
Interruptible
Sumer ventilation is activated. It can be
ventilation
interrupted by RT or 0-10 V input requests.
The heater will try to ignite 2 times before it stops