4.5.4. ON/OFF thermostat installation
To connect the air heater to an ON/OFF room thermostat,
do the following:
Connect the two thermostat wires to terminal 6 and
7 (see figure 9 or the electrical wiring diagram in
§11.). This is a 24 V connection for the thermostat
signal.
Figure 9
- ON/OFF thermostat connection
NOTICE
Never combine these connections with the
terminals 6 and 7 of other air heaters.
NOTICE
Always use separate relays for each air heater.
NOTICE
Do not connect an external power source to
these terminals. These terminals need a dry contact.

5. Flue systems

The air heater is equipped with an internal combined
combustion air supply and a combustion gas outlet device
(wall terminal). Only in this configuration is the installation
is CE approved. Do not change this configuration. See the
installation drawings for more information.
CAUTION!
Never connect another terminal to the
air heater. Always consult the manufacturer or its
representative.
INSTALLATION MANUAL AIR HEATER TYPE DXE