Operation - Gardner Denver RNC100 Instruction Manual

Refrigerated type compressed air dryers
Hide thumbs Also See for RNC100:
Table of Contents

Advertisement

Models 200-750
Manual Draining - Drain valve handle shall be rotated
slightly past the drain isolation position to allow
throttling through the valve for manual discharge
and depressurization.
NOTE: (Models 200-750 only) The quick disconnect
fitting allows removal of the entire drain assembly.
However, the unit must be depressurized prior
to disassembly or serious injury may occur.
NOTE: Discharge is at system pressure. Drain line should be
anchored.
NOTE: Condensate may contain oil. Comply with applicable
laws concerning proper disposal.
I - Controller Level 1 - Model 100 (Standard)
On/Off
Power On
Switch
I - Controller Level 2 - Model 100 (Optional)
On/Off
Power On
Compressor On
Switch
Light
Switch Legend
MRD200-750
Dew Point
Light
Indicator
Models 125-750 (Standard)
Dew Point
Light
Temperature
Indicator
Drain
Push-to-Test
33F......................39F
1C.......................4C
Condensate
Draining

2.0 OPERATION

2.1 Minimum/Maximum operating conditions
A.
Maximum inlet air pressure: refer to dryer serial number
tag
B.
Minimum inlet air pressure: 30 psig (2.1 kgf/cm
C.
Maximum inlet air temperature: 120°F (49°C)
D.
Maximum ambient temperature:
Air-cooled models: 110°F (43°C)
Water-cooled models: 130°F (54°C)
E.
Minimum ambient temperature: 40°F (4°C)
2.2 Start-up
IMPORTANT: Energize dryer disconnect switch (provided by
others, see NEC) 24 hours before refrigeration compressor
is started! Never use the disconnect switch to shut-down
the dryer for a extended period of time (except for repair).
Failure to follow these instructions may result in a non-
warrantable compressor failure.
NOTE: It is recommended that dryer be started 15 minutes
before compressed air flow begins.
NOTE: If there is no power to the control board for a
period of two weeks or more, it may return to the default
mode.
1.
Confirm On/Off Switch is in the "Off" position.
2.
On water-cooled models: after 24 hours, begin cooling
water flow.
3.
Check for proper electrical voltage.
4.
Energize dryer. Green power-on light will illuminate.
5.
Slowly pressurize unit air side by opening inlet isolation
valve. Check for leaks.
6.
After 15 minutes, open outlet isolation valve slowly.
7.
Close air by-pass valve.
8.
Identify Controller on dryer.
A.
Models with I-Controller Level 1 or 2 - proceed to
Step 9.
B.
For Models with I-Controller Level 4, see Section 2.6
for further instructions.
9.
Toggle ON/OFF switch to the ON position.
)
2
5