4.8

Electrode adjustment

Make sure that the electrodes are positioned as
shown in Fig. 19.
WARNING
4.9

Combustion head setting

The setting of the combustion head depends exclusively on the
maximum burner delivery at which it will be operating.
Turn screw 4)(Fig. 20) until the notch shown in diagram (Fig. 21) is
level with the front surface of flange 5)(Fig. 20).
Example: maximum light oil delivery = 32 GPH
Diagram (Fig. 21) indicates that for a delivery of 32 GPH requires
the combustion head to be set to approx. 6 notches, as shown in
Fig. 20.
20103379