Setting The Limit Switches - GEM 9428000ZG05YS08C1A01015 Operating Instructions Manual

Motorized quarter turn actuator
Table of Contents

Advertisement

12.3 Setting the limit switches

Risk of electric shock
▶ Risk of injury or death (if operating
voltage is higher than safe extra low
voltage).
▶ Adjustments are made with the actu-
ator cover removed.
▶ Electric shock can cause severe burns
and fatal injury.
Always disconnect the product from
power supply!
Therefore, have all work performed
only by qualified electricians.
Destruction of the actuator!
▶ Do not move the right limit switch too far to the right and
the left limit switch too far to the left, otherwise the actu-
ator will continue running in the end position (i.e. the limit
switch cannot be actuated by the lever and the actuator
continues to run).
Tools required for setting the limit switches:
Allen key SW3
Small Philips head screw driver
Always switch the limit switch for signal so that the mo-
tor switch is actuated first.
ð Limit switches for signal and motor are already preset.
Information for use in damp conditions
▶ The product may only be used outdoors in an area protec-
ted from rain.
▶ The product must be protected from the direct influence
of rainwater.
▶ An enclosure is recommended.
www.gemu-group.com
DANGER
CAUTION
NOTICE
NOTICE
NOTICE
The GEMÜ 9428 motorized actuator is delivered in open posi-
tion.
The following drawings differ depending on the actuator ver-
sion!
1. Disconnect the plant from power supply and secure
against recommissioning.
2. Remove the protective caps 1.
3. Undo screws 2.
4. Disassemble the cover of the actuator 3.
5. Undo screws at the respective limit switch (4 = "CLOSED",
5 = "OPEN").
6. Move limit switches to the desired position.
7. Tighten limit switch screws.
27 / 34