GEM 9428000ZG05YS08C1A01015 Operating Instructions Manual page 21

Motorized quarter turn actuator
Table of Contents

Advertisement

10.1.2 ON/OFF actuator with 2 potential-free limit switches (code AE)
12 V DC (code B1) / 24 V DC (code C1)
Position of the connectors
Electrical connection
2
1
3
6
4
5
Plug assignment UV
Pin
Uv+, direction of travel CLOSED
1
Uv-, direction of travel CLOSED
2
Uv+, direction of travel OPEN
3
Uv-, direction of travel OPEN
4
n.c.
5
n.c.
6
PE, protective earth conductor
Connection diagram
External
wiring
CLOSED-0-OPEN
S3
Connection assignment UV
S3
CLOS
Direction of travel CLOSED
ED
0
OFF
OPEN Direction of travel OPEN
www.gemu-group.com
Actuator version
3006, 3015
Description
2
1
3
4
6
5
Uv
Actuator
S1/S2
UV
2
1
3
6
4
5
Plug assignment S1/S2
Pin
1
Change-over contact limit switch CLOSED
2
Make contact limit switch CLOSED
3
Break contact limit switch CLOSED
4
Break contact limit switch OPEN
5
Make contact limit switch OPEN
6
Change-over contact limit switch OPEN
PE, protective earth conductor
OPEN
2
1
4
21 / 34
Description
CLOSED
Additional
2
4
limit switches
2
1
3
4
6
5
10 Electrical connection
1
GEMÜ 9428