Do not put flammable and explosive articles around the inverter.
Warning
4.1.2 The requirements for inverter installation spacing are shown in Figure 4-2:
300mm
Figure 4-2 Recommended installation space
4.1.3 The installation angle of the inverter is recommended as shown in Figure 4-3:
Figure 4-3 Recommended installation angle
24
300mm
300mm
※ 4.2 Mounting the Inverter (Standard bracket)
4.2.1 Wall bracket installation
Dimensions of wall bracket, see Figure 4-4:
150mm
Figure 4-4 Dimensions of wall bracket
① Use the wall bracket as the template to mark the position of 5 holes on the wall. See Fig-
ure 4-5 for details:
Figure 4-5 Mark the hole position
② Use an electrical driller with 10mm diameter bit to drill 5 holes on the wall and make sure
hole depth is 80mm.
300mm
150mm
150mm