FlowCon FH and FH.1 Actuators
1B95036 - 09/2021
Installation and Operation Instruction
The actuator types FlowCon FH and FlowCon
FH.1 are electrical, high force actuators. FH is
all-in-one including 24V modulating, 3-point floating
and 2-position. FH.1 is 24V modulating and
2-position failsafe version.
Fitting and Re-fitting
Do not connect power to the actuator unless
the actuator is already fitted on the valve
and NEVER install the actuator in closed
position - this may damage the valve. Actu-
ator is supplied in open position to ensure
easy commissioning of the system.
Mount the actuator on the valve and finger
tighten the connection union. Do not use addi-
tional tools. In case the actuator will have to be
removed, it is recommended to electrically open
the actuator for easier removal. Hereafter finger
loosen the connection union. Again, no need for
additional tools. Please make sure that the ac-
tuator is electrically opened, before re-fitting it on
the valve.
Figure 1
This paper is a supplement to the FlowCon General Instruction
Latest release of any FlowCon material is available on www.flowcon.com
Figure 2
Orientation
Upside-down installation is allowed along with
the standard horizontal and vertical installation.
360º
Figure 3
Page 1 of 4

Advertisement

loading

Summary of Contents for FlowCon FH

  • Page 1 Please make sure that the ac- tuator is electrically opened, before re-fitting it on the valve. Figure 3 Figure 1 This paper is a supplement to the FlowCon General Instruction Page 1 of 4 Latest release of any FlowCon material is available on www.flowcon.com...
  • Page 2 (max. 215 sec). Hereafter the proceed to normal operation mode. actuator will return to normal operation mode. This paper is a supplement to the FlowCon General Instruction Page 2 of 4 Latest release of any FlowCon material is available on www.flowcon.com...
  • Page 3 Normally Open Normally Closed Control signal 2-10V Control signal 0-10V Auto cycle ON Auto cycle OFF This paper is a supplement to the FlowCon General Instruction Page 3 of 4 Latest release of any FlowCon material is available on www.flowcon.com...
  • Page 4 10V-2V-10V-2V- 10V-2V to achieve re-calibration. After re-calibration the actuator will go into normal operation mode. This paper is a supplement to the FlowCon General Instruction Page 4 of 4 Latest release of any FlowCon material is available on www.flowcon.com...