DAV TECH PCP Operating Instructions Manual page 14

Olumetric pump drive
Table of Contents

Advertisement

Operating instructions
4.4 Power supply
The drive power supply will be 24VDC as it is also the rated voltage of the motor.
The drive has 2 separate power supplies, one for the logic and one for the power, this is to make
it possible to cut the power of the pump from a safety circuit, even if the pump is not considered
dangerous as it has no moving part on the outside. The maximum absorption for a PCP pump is
about 2.5 A while the drive logic is about 200-300mA.
It is advisable to use cables with a minimum section of 1 mm² for connections with a length of less
than 20 m and at least 2.5 mm2 in the case of connections with a longer length (maximum length
allowed = 20 m).
Use 4- core twisted pair and shielded cables.
4.5 Ground connections
It is preferable to use a ground bar that acts as a collector especially if there are several drives
connected.
It is important to connect to ground:
• the gnd of the power supply
• the drive housing
• the expected connection provided on the power terminal board
• the power cable screen (connected via the terminal of the power terminal board)
• the encoder cable screen.
4.6 Power connector
The power connector is used to:
• bring power to the drive
• connection of the motor power supply
The connector carries the following wire diameters and tips
CONDUCTOR CHARACTERISTICS
Rigid conductor section
Flexible conductor section
Flexible conductor cross section with cable lug without collar
Flexible conductor section with ferrule with collar
Stripping length or cable lug length
mm
2
0,2 - 2,5
0,2 - 2,5
0,2 - 2,5
0,2 - 2,5
10