Table 7 Charge Mode Specifications
Nominal Input Voltage
Input Voltage Range
High Voltage Disconnect
High Line Re-connect
Low Voltage Disconnect
Low Line Re-connect
Nominal Output Voltage
Nominal Charge Current
Charge current tolerance
Over Charge Protection
Charge Algorithm
Battery Type Setting(+/-0.3v/bat)
Charger current (+/-10%)
Note: NOR – Normal range; GEN-Generator range; WID-Wide range
100V - 270Vac(GEN/WID)
Refer to Charge Algorithm/ Battery Type Setting
Bat. V ≥30Vdc, Fault, Buzzer alarm
Three stage:
Boost CC (constant current stage) → Boost CV (constant voltage
stage) → Float (constant voltage stage)
Battery Type
Flooded
AGM / Gel
14
230Vac
180V - 270Vac(NOR)
280Vac±4%
270Vac±4%
170Vac(NOR)
90Vac(GEN/WID)
180Vac±4% (NOR)
100Vac±4% (GEN/WID)
10A @Vi/p<170Vac
20A@Vi/p=230Vac
10A @Vi/p>280Vac
±10%
Boost CC/CV
Voltage(V)
24
29.2
28.2
Float
Voltage(V)
24
27.0
27.0