SPECIFICATIONS
Table 5 Line Mode Specifications
MODEL
Input Voltage Waveform
Nominal Input Voltage
Low Line Disconnect
Low Line Re-connect
High Line Disconnect
High Line Re-connect
Max AC Input Voltage
Nominal Input Frequency
Low Line Frequency Disconnect
Low Line Frequency
Re-connect
High Line Frequency Disconnect
High Line Frequency Re-connect
Output Voltage Waveform
Output Short Circuit Protection
Efficiency (Line Mode)
Transfer Switch Rating
Transfer Time
Bypass charger enable in off mode
Power Limitation
Sinusoidal (utility or generator)
Note: 1.NOR setting can be used for general electrical appliance
2. WID setting can be used only for some special load, such as
lamp, fan.
50Hz / 60Hz (Auto detection)
As same as Input Waveform
>95% ( Rated R load, battery full charged )
10ms (typical) 15ms max(NOR)
20ms (typical) 40ms max(GEN/WID)
12
IPS3000P
230Vac
170Vac±4%(NOR)
90Vac±4%(GEN/WID)
180Vac±4% (NOR)
100Vac±4% (GEN/WID)
280Vac±4%
270Vac±4%
300Vac rms
40±1Hz
42±1Hz
65±1Hz
63±1Hz
30A Circuit Breaker
30A
Yes