Riello RLAS 650/EV Installation, Use And Maintenance Instructions page 29

Dual fuel air atomizing oil/gas burner
Table of Contents

Advertisement

4.12.3 Hydraulic connections
Make sure that the flexible hoses to the pump sup-
ply and return line are installed correctly.
CAUTION
Follow the instructions below:
 tighten the flexible hoses with the supplied gas-
kets.
WARNING
 Take care that the hoses are not stretched or
twisted during installation.
 Place the pipes so that they are not crushed or
are in contact with hot parts of the boiler and so
it is possible to open the burner.
 Finally, connect the other end of the flexible
hoses to the suction and return pipes.
4.12.4 Hydraulic circuit layout
Key (Fig. 24)
1
Pump suction
2
Pump pressure regulator
3
Filter
4
Oil pressure gauge
5
Min. Oil pressure switch
6
Safety valve
7
Discharge valve
8
Control valve
9
Oil modulator
10 Air solenoid valve
11 Air pressure switch
12 Air pressure gauge
13 Nozzle
14 Max oil pressure switch
P
Pressure gauge connection
V
Vacuometer connection
OPERATION
Pre-purging phase: valves 6) closed.
Ignition and operation phase: valves 6) opened.
Stop: all valves closed.
4.12.5 Pressure variator
The pressure variator (Fig. 25), incorporated in the oil circuit valve
group, makes it possible to vary the pressure on the nozzle line de-
pending on the output required. The pressure on the nozzle line is
adjusted by varying a section by means of the rotation of the ser-
vomotor, which also controls the gas butterfly valve at the same
time.
 Regulator to 0° (minimum opening) = minimum pressure on
nozzle line.
 Regulator to 90° (maximum opening) = maximum pressure on
nozzle line.
The servomotor is controlled by the electronic cam; thanks to this
device, it is possible to set different curves for oil and gas on the
same servomotor (also for the air damper servomotor.
 When adjusting the gas, it is recommended to adjust the servo-
motor to about 90° to reduce leaks from the gas butterfly valve.
 When adjusting the oil, the adjustment is done based on the
nozzle fitted and on the required degree of modulation; in a sit-
uation of minimum firing rate, a rotation of 20° can be enough.
Installation
1/2" NPT
5
6
4
3
V
P
1
2
OUTLET
Key (Fig. 25)
1
Outlet pressure gauge
2
Position indicator (0 ÷ 90) of the pressure variator
3
Max oil pressure switch
27
GB
Air Valve
10
12
8
11
14
6
4
4
9
7
8
3
2
20159158
13
8
20159149
Fig. 24
INLET
1
Fig. 25
20142253