Bryant DuraPac 558F151 Installation, Start-Up And Service Instructions Manual page 47

Single package rooftop electric heating / electric cooling unit
Table of Contents

Advertisement

Table 23 — Fan Performance 558F102,103 — Horizontal Discharge Units; Standard Motor (Belt Drive)*
AIRFLOW
0.2
(Cfm)
Rpm
Bhp
2200
459
0.41
2250
465
0.43
2300
471
0.45
2400
483
0.49
2500
495
0.54
2550
501
0.56
2600
507
0.59
2700
519
0.64
2800
532
0.70
2900
544
0.75
3000
557
0.82
3100
570
0.88
3200
583
0.95
3300
596
1.03
3400
609
1.10
3500
622
1.19
3600
635
1.27
3700
649
1.36
3750
655
1.41
3800
662
1.46
3900
675
1.56
4000
689
1.66
4100
703
1.77
4200
716
1.89
4250
723
1.95
AIRFLOW
1.2
(Cfm)
Rpm
Bhp
2200
802
1.57
2250
806
1.60
2300
811
1.64
2400
819
1.71
2500
828
1.79
2550
832
1.83
2600
836
1.88
2700
845
1.96
2800
854
2.05
2900
864
2.15
3000
873
2.24
3100
882
2.35
3200
3300
3400
3500
3600
3700
3750
3800
3900
4000
4100
4200
4250
LEGEND
Bhp
— Brake Horsepower Input to Fan
Watts — Input Watts to Motor
*Motor drive range: 685 to 935 rpm. All other rpms require field-
supplied drive.
All manuals and user guides at all-guides.com
EXTERNAL STATIC PRESSURE (in. wg)
0.4
Watts
Rpm
Bhp
Watts
384
550
0.62
575
402
555
0.64
596
421
560
0.66
618
461
571
0.71
665
503
581
0.77
715
526
587
0.79
740
549
592
0.82
767
597
603
0.88
823
649
614
0.95
882
703
625
1.01
944
761
637
1.08
1009
823
648
1.16
1079
888
660
1.23
1151
957
672
1.32
1228
1030
684
1.40
1308
1106
696
1.49
1392
1187
708
1.59
1481
1272
720
1.69
1573
1316
726
1.74
1621
1361
732
1.79
1670
1454
745
1.90
1771
1553
757
2.01
1877
1655
770
2.13
1988
1762
782
2.25
2103
1818
789
2.32
2162
EXTERNAL STATIC PRESSURE (in. wg)
1.4
Watts
Rpm
Bhp
Watts
1461
852
1.83
1711
1494
856
1.87
1747
1528
860
1.91
1784
1599
868
1.99
1859
1672
877
2.08
1938
1710
881
2.12
1979
1749
885
2.17
2021
1830
894
2.26
2107
1914
903
2.36
2197
2002
2093
2189
0.6
Rpm
Bhp
Watts
Rpm
625
0.83
778
690
629
0.86
802
694
634
0.89
828
699
644
0.94
881
708
654
1.01
937
717
659
1.04
967
722
664
1.07
996
727
674
1.14
1059
737
684
1.21
1125
746
695
1.28
1194
756
705
1.36
1266
766
716
1.44
1342
776
727
1.53
1422
787
738
1.61
1506
797
749
1.71
1593
808
760
1.81
1685
818
771
1.91
1781
829
783
2.02
1881
840
789
2.07
1932
794
2.13
1985
806
2.25
2093
818
2.37
2207
1.6
Rpm
Bhp
Watts
Rpm
899
2.11
1971
943
903
2.15
2009
907
2.20
2048
915
2.28
2129
923
2.37
2214
NOTES:
1. Boldface indicates field-supplied drive is required.
2. Maximum continuous bhp is 2.40.
3. See page 33 for general fan performance notes.
47
0.8
1.0
Bhp
Watts
Rpm
Bhp
1.07
994
748
1.31
1.10
1021
753
1.34
1.13
1050
757
1.38
1.19
1109
766
1.45
1.26
1171
775
1.52
1.29
1204
779
1.56
1.33
1237
784
1.60
1.40
1306
793
1.68
1.48
1378
803
1.76
1.56
1453
812
1.85
1.64
1533
822
1.94
1.73
1615
831
2.03
1.82
1702
841
2.13
1.92
1792
851
2.24
2.02
1887
861
2.35
2.13
1985
2.24
2088
2.35
2195
1.8
2.0
Bhp
Watts
Rpm
Bhp
2.40
2241
Watts
1221
1252
1283
1348
1416
1452
1488
1563
1641
1723
1808
1897
1991
2088
2188
Watts

Advertisement

Table of Contents
loading