Fig. 3 — Unit Leveling Tolerance
HORIZONTAL
DRAIN OUTLET
NOTE: Drain plug is shown in factory-installed position.
Fig. 4 — Condensate Drain Connection (Side View)
NOTES:
1. Dimension in ( ) is in millimeters.
2. Hook rigging shackles through holes in base rail, as shown in detail
''A.'' Holes in base rails are centered around the unit center of grav-
ity. Use wooden top skid when rigging to prevent rigging straps
from damaging unit.
3. Unit weights do not include economizer. See Tables 1A and 1B for
unit weight of economizer.
CAUTION:
All panels must be in place when rigging. Unit
is not designed for handling by a fork truck. Damage to unit may
result.
All manuals and user guides at all-guides.com
MAXIMUM ALLOWABLE
DIFFERENCE (in.)
A-B
B-C
A-C
0.5
1.0
1.0
DRAIN PLUG
Fig. 6 — Rigging Details
NOTE: Trap should be deep enough to offset maximum unit static differ-
ence. A 4-in. trap is recommended.
Fig. 5 — Condensate Drain Piping Details
OPERATING
UNIT
WEIGHT
558F
lb
kg
090,091
755
342
102,103
760
345
120,121
915
415
150,151
930
422
4
DIMENSIONS
''A''
''B''
in.
mm
in.
mm
77.42 1967 40.25 1022 41.31 1050
77.42 1967 40.25 1022 41.31 1050
77.42 1967 40.25 1022 49.31 1253
77.42 1967 40.25 1022 49.31 1253
''C''
in.
mm