Bryant DuraPac 558F151 Installation, Start-Up And Service Instructions Manual page 30

Single package rooftop electric heating / electric cooling unit
Table of Contents

Advertisement

CO
Sensor Configuration
2
The CO
sensor has preset standard voltage settings that
2
can be selected anytime after the sensor is powered up. See
Table 5.
Use setting 1 or 2 for Bryant equipment. See Table 5.
1. Press Clear and Mode buttons. Hold at least 5 sec-
onds until the sensor enters the Edit mode.
2. Press Mode twice. The STDSET Menu will appear.
3. Use the Up/Down button to select the preset number.
See Table 5.
4. Press Enter to lock in the selection.
5. Press Mode to exit and resume normal operation.
The custom settings of the CO
time after the sensor is energized. Follow the steps below to
change the non-standard settings:
1. Press Clear and Mode buttons. Hold at least 5 sec-
onds until the sensor enters the Edit mode.
2. Press Mode twice. The STDSET Menu will appear.
SETTING
EQUIPMENT
1
Interface w/Standard
2
Building Control System
3
4
5
Economizer
6
7
8
Health & Safety
Parking/Air Intakes/
9
Loading Docks
LEGEND
ppm — Parts Per Million
All manuals and user guides at all-guides.com
sensor can be changed any-
2
Table 5 — CO
2
VENTILATION
OUTPUT
RATE
(cfm/Person)
Proportional
Any
Proportional
Any
Exponential
Any
Proportional
15
Proportional
20
Exponential
15
Exponential
20
Proportional
Proportional
3. Use the Up/Down button to toggle to the NONSTD
menu and press Enter.
4. Use the Up/Down button to toggle through each of
the nine variables, starting with Altitude, until the
desired setting is reached.
5. Press Mode to move through the variables.
6. Press Enter to lock in the selection, then press Mode
to continue to the next variable.
Dehumidification of Fresh Air with DCV Control
Information from ASHRAE indicates that the largest humid-
ity load on any zone is the fresh air introduced. For some
applications, a device such as an energy recovery unit is
added to reduce the moisture content of the fresh air being
brought into the building when the enthalpy is high. In most
cases, the normal heating and cooling processes are more
than adequate to remove the humidity loads for most com-
mercial applications.
If normal rooftop heating and cooling operation is not ade-
quate for the outdoor humidity level, an energy recovery unit
and/or a dehumidification option should be considered.
Sensor Standard Settings
CO
ANALOG
CONTROL RANGE
OUTPUT
(ppm)
0-10V
0-2000
4-20 mA
2-10V
0-2000
7-20 mA
0-10V
0-2000
4-20 mA
0-10V
0-1100
4-20 mA
0-10V
0- 900
4-20 mA
0-10V
0-1100
4-20 mA
0-10V
0- 900
4-20 mA
0-10V
0-9999
4-20 mA
0-10V
0-2000
4-20 mA
30
OPTIONAL
2
RELAY SETPOINT
(ppm)
1000
1000
1100
1100
900
1100
900
5000
700
RELAY
HYSTERESIS
(ppm)
50
50
50
50
50
50
50
500
50

Advertisement

Table of Contents
loading

Table of Contents