5.6
Securing the burner to the boiler
Provide an adequate lifting system of the burner.
5.6.1
Hinge installation
Install the hinge 4), supplied as standard, as shown in Fig. 8.
S7392
Separate the combustion head assembly from the burner
5.7
Positioning the probe - electrode
Do not turn the ignition electrode but leave it as
shown in Fig. 10.
If the ignition electrode is put near the ionisation
WARNING
probe, the control box amplifier might be dam-
aged.
~
40 mm
Probe
D5070
20063692
Installation
4
Fig. 8
Probe
2.2
Diffuser
14
GB
body by removing nut 1) and removing the group A)(Fig. 9).
Fix the group B)(Fig. 9) to the boiler plate 2), inserting the
supplied insulating gasket 3).
The seal between burner and boiler must be
airtight.
WARNING
A
Respect the positions shown in Fig. 10.
WARNING
Electrode
1
3
D5108
B
Electrode
2.5 - 3.5 mm
Fig. 10
2
Fig. 9