4.4
Technical data
Model
Heat output (Hi)
(1)
Fuel
Operation
Use
Ambient temperature
Combustion air temperature
Electrical supply
Fan motor
Ignition transformer
Capacitor
Absorbed electrical power
Protection level
Weight
Noise levels
Sound pressure
(2)
Sound power
Reference conditions: Room temperature 20°C - Gas temperature 15°C - Barometric pressure 1013 mbar - Altitude 0 m a.s.l.
(1)
Sound pressure measured in manufacturer's combustion laboratory, with burner operating on test boiler and at maximum rated output. The sound
(2)
power is measured with the "Free Field" method, as per EN 15036, and according to an "Accuracy: Category 3" measuring accuracy, as set out in
EN ISO 3746.
For gas family 3 (LPG) ask for separate kit.
WARNING
4.5
Maximum dimensions
The maximum dimensions of the flange and burner are given in
Fig. 1.
Flange
Ø 185
130
D5106
Model
RIELLO 40 FS8
RIELLO 40 FS8 TL
20063692
Technical description of the burner
kW
min - max
kcal/h
Family 2
°C
°C max
rpm - rad/s
V - Hz
W
A
F
kW
kg
dB(A)
305
L (mm)
110
170
Tab. D
RIELLO 40 FS8 - FS8 TL
40.000 80.000
NCV 8 12 kWh/m
Pressure: min. 12 mbar – max. 360 mbar
Intermittent (FS1)
Boilers: water and diathermic oil
1/230V/50Hz
2800 - 294
Primary 230V / 0.2A – Secondary 8 kV
Burner
33
8
GB
46 93
3
– 7,000 10,340 kcal/m
0 - 50
60
230 - 50
90
0.75
4
0.15
IP40
13
63.1
74.7
L
347
61
3
Tab. C
Fig. 1