Page 4
Document: LT0712 END USER LIABILITY DISCLAIMER Some of the operation of QE20 Emergency Warning System as described in this manual is dependent on site-specific configuration performed by the field engineer. If the configuration is not well-designed, then operation may differ from this manual and compliance to local installation standards may be invalidated.
Example Site Configuration ..................... 3-1 Circuit Usage Report ......................3-2 On-Site Programming ..................4-1 What’s Available ....................... 4-1 Placing Into Operation ................... 5-1 Initial Power Up ......................... 5-1 Check Field Wiring Before Connecting to QE20 ............5-1 Issue 1.0 13 June 2023 Page iii...
Page 6
Document: LT0712 Commissioning ......................... 5-2 Fault Finding ........................5-4 Spare Parts, Drawings ................... 6-1 Spare Parts ........................6-1 Drawings ..........................6-2 Module Installation ..................7-1 Installation Guide For Each QE20 Module ..............7-1 Page iv 13 June 2023 Issue 1.0...
– in terms of the number of zones, amplifiers and power rating, power supplies, field wiring modules, and optional networking. A block diagram is shown in Figure 1. QE20 is highly configurable and expandable up to 224 emergency zones on the user interface.
Page 8
Fibre Network kit. Each QE20 will be supplied in one or more 19” rack mounting cabinets, with a Perspex window in the outer doors and the user interface mounted on hinged inner doors.
Page 9
Figure 2 shows an example front panel view, and Figure 3 an internal view. Figure 2 Example QE20 Front View Issue 1.0 13 June 2023...
Page 10
QE20 Installation Manual Document: LT0712 Figure 3 Example QE20 Internal View Page 1-4 13 June 2023 Issue 1.0...
40U SECP (Shallow – 165mm) 1863 x 575 x 213 mm The QE20 could also be supplied as a “Combo” panel, where both a fire alarm system and the QE20 are installed in a single 40U deep cabinet. Handling & Checking Cabinets Precautions should be taken when handling the QE20 cabinets, as they can be of significant weight.
• Have an ambient noise level of not more than 70 dB(A), • Not exceed the ambient operating conditions for the QE20, • Allow all the controls and indications of the QE20 to be within 750 mm and 1850 mm of the floor, •...
Consideration should be given to future expansion of the QE20 at the time of selecting and installing the mains supply. The following table shows the recommended circuit breaker rating and...
1.5mm 2.5mm 2.5mm The mains wiring to the QE20 cabinet is terminated in the single dual-outlet GPO (1- 2 PSE) or two dual-outlet GPOs (3-4 PSE). The GPO terminal capacity is a maximum of 3 x 2.5mm conductors, so fitting the incoming mains wire and a wire across to the other GPO is possible.
LM0652 to the positive terminal. Do not connect the Anderson connector until the QE20 has been initially powered up and tested. Wiring to a remote battery is not permitted.
Adjacent Cabinet Wiring Where a QE20 system consists of multiple adjacent cabinets it will be necessary to reconnect the factory fitted wiring between the cabinets. Long connecting cables will be included in any additional cabinets, to allow connection to the previous cabinet.
QE20s when copper cabling is used. If fibre cabling is used, then additional equipment will be fitted to the QE20 to transport the audio signals over the fibre network.
• Command Scripts table – Description for GUI / User Buttons field. Alternatively, there is a preformatted label, LB0694, that is available from the Fireplace website (vigilant-fire.com.au) as an editable PDF file and an AutoCAD drawing. Enter the required button descriptions into these forms and print them off.
Page 24
QE20 Installation Manual Document: LT0712 THIS PAGE INTENTIONALLY LEFT BLANK Page 2-10 13 June 2023 Issue 1.0...
• Networking with other panels • Phased evacuation, messages, etc. A printout of the site configuration is supplied with each QE20 and is the key document defining what function has been assigned to each input and output of the QE20 and thus what field wiring should be connected and where.
The Circuit Usage Report available in QE20Config can be used to list the inputs and outputs assigned and their function. This can assist in terminating the field wiring to the correct terminals, if the wiring is labelled by zone number / location. QE20 Install Manual Example ********Amplifiers*********** Zone...
What’s Available Most site settings are entered into QE20Config to form the site configuration. This is downloaded to the QE20 and stored in non-volatile memory in the Controller, so it is available each time the QE20 is turned on. The following items can be configured on-site separately to the site configuration, so may be changed without requiring a computer with QE20Config installed and access to change the configuration.
Page 28
QE20 Installation Manual Document: LT0712 Rotate the knob to obtain the desired volume and touch SET VOL. The amplifier volume will be changed. Check the volume in the area is appropriate. Next time the site configuration is extracted or before it is changed, a prompt will be given to merge the on-site volume settings with the site configuration.
Page 29
CANCEL to abort. Note the background music setting is lost on power down / restart of the QE20 and will be initialised on power up to a state defined by the installer. Issue 1.0...
Page 30
QE20 Installation Manual Document: LT0712 THIS PAGE INTENTIONALLY LEFT BLANK Page 4-4 13 June 2023 Issue 1.0...
• Install the QE20 cabinets and complete the mains power wiring to the cabinets. If permanent mains wiring is not available, temporary wiring may be used as long as the QE20 has no VADs or 100V loads connected (so the power consumption is minimal).
QE20Config or manually filled in from the configuration) and fit to the pockets in the user interface. The general steps for commissioning a QE20 are as follows (also refer to each QE20 module installation guide for specific commissioning instructions). • For each evacuation zone:...
Page 33
Activate an appropriate zone alarm (or test the zone) on the fire panel and check the correct zone on the QE20 goes into alarm. Reset the alarm at the fire panel, then Reset the alarm on the QE20 and check all zones are normal.
QE20 Installation Manual Document: LT0712 Check that the fault on the QE20 generates a fault on the fire panel if the fire panel monitors the QE20 for faults. • With no batteries connected put all zones (or at least those in each cabinet) into evacuate at the same time.
Document: LT0712 QE20 Installation Manual Spare Parts, Drawings Spare Parts Note most QE20 products are labelled with the part number of their replacement part. Part Number QE20 Module Spare / Additional Item FP2000 QE20 Controller Module FP2001 QE20 27A Power Supply Equipment (PSE)