Dhw Storage Tank; Solar Controlling - andrews COMBIflo 100/300 Manual

Indirect high efficiency boiler & stainless steel storage water heater
Table of Contents

Advertisement

Menu: Configuration
Solar controlling element
In place of a collector pump and diver-
ting valves for integrating the storage
tanks, the solar plant can also be ope-
rated with charging pumps.
External solar exchanger
In the case of solar plants with 2 stora-
ge tanks, it must be selected whether
there is an external heat exchanger
used for both the DHW and the buffer
storage tank, or for 1 of them only.
Combi storage tank
Functions specific to combi storage
tanks are activated with this setting. For
example the electric immersion heater
in the buffer storage tank can be used
for both space heating and DHW hea-
ting.
Andrews COMBIfl o
Line no.
5840
Solar controlling element
Charging pump
Diverting valve
Charging pump
When using a charging pump, all heat
exchangers can be used at the same
time. Either parallel or alternative ope-
ration is possible.
Line no.
5841
External solar exchanger
Jointly

DHW storage tank

Buffer storage tank
Line no.
5870
Combi storage tank
No
Yes
No
No combi storage tank present.
31
Operating line
Diverting valve
When using a diverting valve, it is al-
ways only 1 heat exchanger that can be
used at a time. Only alternative operati-
on is possible.
Operating line
Operating line
Yes
Combi storage tank present.
Factory setting
Charging pump
Factory setting
Jointly
Factory setting
No
Controls programming guide

Advertisement

Table of Contents
loading

This manual is also suitable for:

Combiflo 150/300

Table of Contents