Chimney Sweep And Manual Control Functions - andrews COMBIflo 100/300 Manual

Indirect high efficiency boiler & stainless steel storage water heater
Table of Contents

Advertisement

Menu: Service/special operation
Chimney sweep function
The burner is started up. To ensure that
burner operation will be as continuous
as possible, only maximum limitation of
the boiler temperature is active to be
used as the switch off point.
To reach the minimum boiler tempera-
ture of 64 °C as quickly as possible, all
consumers are locked for that period of
time by an absolute locking signal.
When the boiler temperature exceeds
64 °C, a forced signal forces all consu-
mers to draw heat so ensure that the
boiler keeps running.
The boiler temperature maximum limi-
tation remains active when chimney
sweeper function is active.
Burner output
Preset burner output for performing the
Chimney sweep function.
Manual control
When manual control is activated, the
relays are no longer energized and
deenergized according to the control
status but are set to a predefined ma-
nual control status in accordance
with their functions (see table).
Setpoint adjustment manual control
After Manual control has been activa-
ted, one should return to the main dis-
play. There the Service/special operati-
on symbol
is displayed.
The setpoint for manual control can be
changed in the info menu, which can be
reached by pushing the info-button.
When manual control is activated, the
relays are no longer energized and
deenergized according to the control
status but are set to a predefined ma-
nual control status in accordance
with their functions (see table below).
The relay outputs are set to a state
where heat is provided, independent of
their hydraulic function. The solar plant
remains switched off since there is a
possibility of storage tank recooling via
the collector. A relay energized in ma-
nual operation can be deenergized by
an electronic control thermostat (TR) or
limit thermostat (TW).
Andrews COMBIfl o
Line no.
Operating line
7130
Chimney sweep function
7131
Burner output
Partial load
Full load
Max heating load
7140
Manual control
Designation
Gas boiler
Solid fuel boiler
Solar
DHW
Instantaneous water heater Charging pump
Buffer storage tank
HC 1..3
Primary controller
External consumer circuits
1..3
Extra function
Cascade
42
Factory setting
Max heating load
Boiler pump
2. stage boiler pump
Solid fuel boiler pump
Collector pump
External exchange pump
Control element buffer
storage tank
Control element swim-
ming pool
Charging pump
Diverting valve
Intermediate circuit pump
DHW mixing pump
Circulation pump
Electric immersion heater
Diverting valve
Heat generation shutoff
valve
Return valve
HC pump
Mixer open/close
HC pump 2. stage
System pump
Prim ctrl mixer open/
close
Consumer circuit pump
Alarm output
Time program 5
Heat demand
Status output
Status information
Flue gas damper
Fan shutdown
Storage tank diverter
pump
Cascade pump
Off
Off
Relay
Status
Q1
On
Q27
On
Q10
On
Q5
Off
K9
Off
K8
Off
K18
Off
Q3
On
Q3
Off
Q33
On
Q35
Off
Q4
On
K6
On
Q34
Off
Q34
Off
Y4
On
Y15
Off
Q2
On
Q6
Q20
Y1/Y2
Off
Y5/Y6
Y11/Y12
Q21
On
Q22
Q23
Q14
On
Y19/Y20
Off
Q15
On
Q18
Q19
K10
Off
K13
Off
K27
On
K35
On
K36
On
K37
On
K38
On
Q11
Off
Q25
On
Controls programming guide

Advertisement

Table of Contents
loading

This manual is also suitable for:

Combiflo 150/300

Table of Contents