6.11.5 Oil pressure switch
Check the calibration of the maximum and minimum oil pressure
switches, using the adjustment screw as shown in Fig. 42.
The check should be carried out by individually varying the cali-
bration of each pressure switch.
Maximum oil pressure switch
Turning the screw anti-clockwise lowers the setting and the burn-
er should go into lockout.
Once this control has been carried out, it is necessary to reset the
factory setting of the maximum oil pressure switch to about 4/5
bar.
Minimum oil pressure switch
Turning the screw clockwise increases the setting and the burner
should not start.
Once this control has been carried out, it is necessary to reset the
factory setting of the minimum oil pressure switch to about 16/18
bar.
Any other pressure values should be adjusted to the burner out-
put.
6.12

Final checks (with burner operating)

 Open the thermostat/pressure switch TL
 Open the thermostat/pressure switch TS
 Turn the gas maximum pressure switch knob to the mini-
mum end of scale position
 Turn the air pressure switch to the maximum end of scale
position
 Check the maximum oil pressure switch
 Check the minimum oil pressure switch
 Turn off the burner and cut off the power
 Disconnect the minimum gas pressure switch connector
 Disconnect the QRI cell wire
Make sure that the mechanical locking systems
on the various adjustment devices are fully tight-
ened.
WARNING
Start-up, calibration and operation of the burner
20079898
The burner must stop
The burner must stop in lockout
The burner must stop in lockout
The burner must not start
The burner must stop in lockout due to ignition failure
37
GB
Fig. 42
Tab. P
20170641