Installation Of Shut-Off Valve Unit - Toshiba RBM-SV1121HUPE Installation Manual

Shut-off valve unit

Advertisement

<Installation space>
RBM-***
A
B
SV1121HUPE
250
250 ( 1)
SV1801HUPE
SV6701HUPE
550 ( 2)
550 ( 2)
( 1) In cace of using the attached pipe (accessory)
350 mm (For SV1121HUPE)
( 2) In cace of using the attached pipe (accessory)
650 mm
EN-11
(Unit : mm)
Bolt size : M10 or Ø3/8
(field supply)
100 or more
A or more
B or more
50 or more
Control Box
Check port
450
3
INSTALLATION OF SHUT-OFF VALVE
UNIT
Install the unit securely in the place to suffi ciently withstand the weight of the unit.
If the foundation is not sturdy enough, the unit may fall and cause personal injury.
Perform a specifi ed installation work to guard against earthquake.
Improper installation may cause the unit to fall.
REQUIREMENT
Strictly comply with the following rules to prevent damage of the Shut-off Valve unit and human injury.
Do not put a heavy article on the Shut-off Valve unit or let a person get on it. (Even units are packaged)
Carry in the Shut-off Valve unit as it is packaged if possible. If carrying in the Shut-off Valve unit unpacked by
necessity, use buffering cloth or other material to not damage the Shut-off Valve unit.
To move the Shut-off Valve unit, hold the hooking brackets (3 positions) only.
Do not apply force to the other parts (refrigerant pipe, drain pan, foamed parts, resin parts or other parts).
Carry the package by two or more persons, and do not bundle it with plastic band at positions other than
specifi ed.
Installation of hanging bolt
Consider the piping / wiring before the unit is hung to determine the location of the Shut-off Valve unit installation
and orientation.
After the location of the Shut-off Valve unit installation has been determined, install hanging bolts.
For the dimensions of the hanging bolt pitches, refer to the external view.
When a ceiling already exists, lay refrigerant pipe, control wires, and remote controller wires to their connection
locations before hanging the Shut-off Valve unit.
Procure hanging bolts washer and nuts for installing the Shut-off Valve unit (these are not supplied).
Hanging bolt
M10 or W3/8
Nut
M10 or W3/8
6
WARNING
3 pieces
9 pieces
EN-12