Connecting in parallel mode

WARNING
The parallel box is sold on request.
Only use the parallel box provided by MOSA.
Connect the parallel box only to the MOSA inverter generators.
The generators must be of the same model. Example: GE 3500 MI with another GE 3500MI
Do not disconnect the parallel cables while the generator is running and the power cables are
connected.
1 - Connect the two generators to the parallel box (1) using the parallel outputs (2).
Red to Red / Black to Black / Earth to Earth connection.
Important
*
Make sure that the cables are connected correctly to the generators.
If they are connected incorrectly, the generators will not deliver any power and you will need to turn
them off and on again after connecting them correctly.
2
2 - Start the first generator and wait for the pilot green warning lamp to light up.
Start the second generator and wait for the pilot green warning lamp to light up on the second generator
as well. For the details, see "6.6.1 Starting the engine".
3 - Take the load from the generators connected in parallel using the sockets on the parallel box.
Note
The power delivered is split halfway between the two generators.
The maximum withdrawable power from the generators connected in parallel is the sum of the rated
powers of each single generator. If the required power exceeds the total sum, the overload protections of
the individual generators will be triggered by removing voltage.
During parallel operation, the AC voltage is also present on the sockets of the generators and it is there-
fore possible to power other equipment.