Setting the torque limit level

Limit the output torque not to exceed the specified value.
The torque limit level can be set in a range of 0% to 400%.
The torque limit level can be selected by using the analog input terminal (terminal 1).
Pr.
Name
22
Stall prevention operation level
H500
(torque limit level)
810
Torque limit input method selection
H700
*1
Initial values differ according to the inverter capacity and the control method. For details, refer to the FR-E800 Instruction Manual
(Function).
NOTE
• The lower limit for the torque limit level under Real sensorless vector control is set to 30% even if a value lower than 30% is
set.
• Under PM sensorless vector control, the torque limit is not activated in a low-speed range with a rated frequency of less than
10%.
• Under PM sensorless vector control, the torque limit level is reduced inversely proportional to the output frequency in the
constant output range of the rated motor frequency or higher.
48
CONTROL CIRCUIT INPUT SIGNAL
Initial value
Setting range
*1
0% to 400%
150% / 200%
0
0
1
2
Description
Set the torque limit level as a percentage with
regards to the rated torque as 100%.
Internal torque limit 1 (torque limited by
parameter settings)
External torque limit (torque limited by terminal 1)
Internal torque limit 2 (torque limited via
communication)