4.0 INSTALLATION
4.1 SPLITTING THE APPLIANCE
If required, the COMBIfl o can temporarily be separated (split) into two parts, manoeuvred and then re-assembled.
Refer to instructions below.
1
5
4
1. Remove LH Front Door - disconnecting Earth Tab before removing.
2. Remove RH Front Door - disconnect the Electrical loom, and remove from 2 cable
retaining clips before removing.
3. Disconnect Tank Sensor Electrical loom.
4. Close Tank Isolation Valves at high and low level.
5. Disconnect Tank connections at high and low level. (BEWARE: Water may still be
present in pipework and leak whilst disconnecting) Retain tank connection washers.
6. Remove 6 connection plates, (3 on front & 3 on back).
7. Unit can now be pulled apart.
8. Re-assembly is the reverse of above. Remember to open any Isolation Valves you
have closed.
LH HEATER SECTION
100 Weight = 175 kg
1090mm(L) x 655mm(W) x 1950mm(H)
ANDREWS COMBIfl o DRAFT
2
4
SPLIT UNIT WEIGHT & DIMENSIONS
RH TANK SECTION
150 Weight = 205 kg
100 Weight = 85 kg
600mm(L) x 600mm(W) x 1950mm(H)
5
150 Weight = 85 kg
7
19
3
6
GB/IE