Acceptance Test And Acceptance Test Report; Commissioning; Operation; System Documentation - Bartec PSB Design Manual

Self-regulating trace heating systems for hazardous/industrial applications
Hide thumbs Also See for PSB:
Table of Contents

Advertisement

Acceptance test and acceptance test report

After completion of the installation work (before installation of the thermal insulation) each heating circuit must be accepted, if possible in the
presence of the client.
All further tests must also be documented in an acceptance test report (refer to section Acceptance report / Record of inspection on page 40).
NOTICE
Claims under warranty will not be considered if the acceptance report is not filled in completely.
After completion of work on the thermal insulation final inspection and acceptance of the individual heating circuits is recommended. Usually,
this is the task of the client or the final customer (= final inspection).

Commissioning

Each heat tracing system can only be put into operation if the following conditions are fulfilled:
The acceptance test reports for each heating circuit are complete and the trace heating system has been accepted.
All components of the heating circuit are completely installed and are in working order.
It has been ensured that the heating circuit is operated in conformance with the technical data specified by BARTEC.
It has been ensured that the trace heating system parameters (as indicated in design documenation) will be verified during commissioning.
NOTICE
Upon a cold start, additional heating power is required for heating up tanks and pipes. When starting the system you should allow sufficient time
for heat up. For further information on heat up calculations contact your local BARTEC representative.

Operation

During operation of the electric trace heating system you must ensure that all components of the system are operated within the operating data
specified by BARTEC.
This applies particularly to observation of the maximum temperature. Operation within these operating data is a precondition for possible later
warranty claims.

System documentation

Complete documentation must be carried out for each system, from the project planning stage, through installation and commissioning up to
periodic maintenance of the trace heating system.
This documentation should include the following:
Project planning documents
Results of design calculation e.g. summarized in Print out of Heloc Pro calculation or Manual calculation documented e.g. in BARTEC template
21-1000-7E0001 (www.bartec.com) In detail:
Trace heating circuit identification
o
Pipe size or workpiece dimensions
o
Maximum ambient temperature
o
Maximum workpiece temperature
o
Temperature to be maintained or the maximum process/exposure temperature
o
Thermal insulation type/size and thickness
o
Thermal insulation cladding if applicable
o
Heat loss calculation
o
Selection of trace heater type
o
Operating voltage
o
Temperature class or maximum sheath temperature
o
Layout plans with sections of heating circuits
o
Trace ratio
o
Circuit graphs (e.g. Circuit diagram or single line diagram)
o
Manuals of all of the components of the heating system
Acceptance reports
Reports on repairwork and any operations carried out on the tank/pipe system, trace heating system and thermal insulation
Inspection reports
21-1S00-7D0001/-
05/2023-EHT-466853
Notice Technical data subject to change without notice.
No claims for damage arising from alternations, errors or misprints shall be allowed.
Page 37 / 42

Advertisement

Table of Contents
loading

Table of Contents