3PSB
Enclosure / trace heater
PBS/PBM
202
ESTM
202
PBTC
202
PBTW
202
Enclosure /
3MSB
trace heater
PBS/PBM
231
ESTM
231
PBTC
231
PBTW
231
For the ESTM temperature controller, the

Selection of the required components for power connection, control and monitoring, end termination etc.

A typical heating circuit with self-regulating trace heaters consists of:
Power supply / cold lead cable connection
Trace heater splices / junctions (optional)
Control and monitoring units (optional)
End termination
Step 11: Determine the required trace heater power connection kit:
→ Example
 From Step 10: 1 Heating circuit with 1 power connection kit = PBS-200-E
Step 12: Determine if control equipment is required:
BARTEC provides a variety of control products, from simple mechanical thermostats to sophisticated digital controllers and control and monitor-
ing systems designed specifically for use with our trace heating products. This section will help you select and specify the right control products
for your application.
General design considerations for temperature control:
When designing your trace heating system, you should consider the following factors.
Adding control elements increases the installation and maintenance costs of the heating system, but allows tighter temperature control, energy
savings and more efficient use of plant maintenance personnel's time.
The thermal environment of a trace heating system varies greatly, especially at valves, pipe supports, and other heat sinks. It is therefore sel-
dom possible to achieve very tight temperature control.
The temperature of a heat tracing system is based on ambient temperature and can vary by as much as 20 °C when the system is uncon-
trolled. You can choose between 2 approaches for temperature control:
21-1S00-7D0001/-
05/2023-EHT-466853
Table G2: Maximum heating circuit length at maximum ambient temperature of the enclosure
+40°C
5PSB
8PSB
165
128
165
128
165
128
165
128
MSB trace heaters, Operating voltage: 230 Vac
+40°C
5MSB
10MSB
15MSB
188
133
82
188
111
80
188
132
82
188
111
80
Maximum heating circuit length
Notice Technical data subject to change without notice.
No claims for damage arising from alternations, errors or misprints shall be allowed.
PSB trace heaters, Operating voltage: 230 Vac
10PSB
3PSB
97
202
97
202
97
202
97
202
20MSB
3MSB
75
231
63
231
74
231
63
231
table please refer to the instructions manual of the ESTM.
+55°C
5PSB
8PSB
165
128
165
128
165
128
165
128
+55°C
5MSB
10MSB
15MSB
188
133
82
188
108
77
188
92
66
188
123
82
10PSB
97
97
97
97
20MSB
75
61
52
70