Operating instructions 1. Product description 3. Safety Instructions The PSB type 27-1680-..10/..Ex heating system with the The relevant installation and operating regulations must be PSB (type 07-5801..) self-limiting parallel heating tape, assembled observed for electrical systems in hazardous areas (e.g. Directive with a connection and remote end termination system (installation kit 1999/92/EC, Directive 94/9EC, EN 60079-14, EN 61241-14 and the 05-0091-0130 and/or 05-0091-0136) in cold connection technology, is...
Page 4
The heating systems must be used only in accordance with their intended insulation resistance between the heating conductor and the metallic purpose and within the operating data specified by BARTEC. braid must be verified. The operator of an electrical system in a hazardous environment must keep...
The following components were used: The type label is to be filled in manually on the basis of the table and PSB 120 V 26 W; Cold-applied connection technology and BARTEC points 1-6. The blanks in the heating system’s type number must be filled polyester junction box.
Page 6
The external dimensions of the enclosure must conform to the specified minimum dimensions. Certification of „e“ increased safety type of protection in compliance with EN 60079-7 must be presented for all components. Requirements set for non-BARTEC enclosures Material Polyester Aluminium...
Declaration of Conformity EN 7/12 Reservation Technical data subject to change without notice. Changes, errors and misprints may not be used as a basis for any claim for damages.
Installation instructions Connection Installation kit 05-0091-0129/05-0091-0135 The dimensions specified in the installation instructions must be strictly observed! Cut the heating tape with a straight cut. Push on the cap for screw connection a and sealing b. Remove 145 mm of the protective outer sheath from the heating tape.
Page 9
Twist the metal braid covering. Pull the strands out and twist them. Remove the remaining heating element. (Fig. 7 and 8) Push the green/yellow heat shrinkable tubing e (150 mm) onto Cut out a triangle (5 mm) between the strands. Put some silicone adhesive h onto the exposed heating element, the insulating the twisted metal braid covering.
Page 10
Installation instructions Remote end termination Screw the screw connection body a in the enclosure. Push the grounding strap c over the thread and secure it with a nut Take the metal braid covering off the end of the heating cable. b.