Maximum Heating Capacity Table for LC098HV (LCN098HV4 + LUU090HV)
Table 38: LCN098HV4 / LUU090HV Maximum Heating Capacities.
Outdoor Air Temp.
°F DB
°F WB
-13
-13.4
-4
-4.4
0
-0.4
5
4.5
10
9
17
15
20
19
25
23
30
28
35
32
40
36
45
41
47
43
50
46
55
51
60
56
63
59
68
64
DB: Dry Bulb Temperature (°F)
WB: Wet Bulb Temperature (°F)
PI: Power Input (kW) (includes compressor, indoor fan motor and outdoor fan motor)
1. All capacities are net, evaporator fan motor heat is deducted.
2. Direct interpolation is permissible.
Do not extrapolate.
3. Grey shading indicates reference data. When operating at this temperature, these values can be
different if the system is not running consistently.
Maximum Heating Capacity Table for LC128HV (LCN128HV4 + LUU120HV)
Table 39: LCN128HV4 / LUU120HV Maximum Heating Capacities.
Outdoor Air Temp.
°F DB
°F WB
-13
-13.4
-4
-4.4
0
-0.4
5
4.5
10
9
17
15
20
19
25
23
30
28
35
32
40
36
45
41
47
43
50
46
55
51
60
56
63
59
68
64
DB: Dry Bulb Temperature (°F)
WB: Wet Bulb Temperature (°F)
PI: Power Input (kW) (includes compressor, indoor fan motor and outdoor fan motor)
1. All capacities are net, evaporator fan motor heat is deducted.
2. Direct interpolation is permissible.
Do not extrapolate.
3. Grey shading indicates reference data. When operating at this temperature, these values can be
different if the system is not running consistently.
61
64
TC
PI
TC
PI
8.71
1.11
8.51
1.15
9.67
1.19
9.46
1.23
10.18
1.23
9.95
1.27
10.81
1.29
10.57
1.33
11.22
1.26
10.97
1.31
11.77
1.24
11.51
1.29
11.94
1.21
11.68
1.25
12.11
1.17
11.84
1.20
12.32
1.12
12.05
1.15
12.49
1.08
12.21
1.11
12.66
1.04
12.38
1.07
12.87
0.99
12.58
1.02
12.95
0.97
12.66
1.00
12.99
0.96
12.73
0.99
13.05
0.95
12.84
0.98
13.12
0.94
12.95
0.96
13.16
0.94
13.01
0.95
13.19
0.93
13.08
0.94
TC: Total Capacity (kBtu/h)
61
64
TC
PI
TC
PI
8.65
1.17
8.46
1.20
9.93
1.25
9.71
1.29
10.61
1.30
10.37
1.34
11.45
1.36
11.20
1.40
12.00
1.36
11.74
1.40
12.74
1.36
12.45
1.40
13.29
1.36
12.99
1.40
13.84
1.36
13.53
1.41
14.53
1.37
14.20
1.41
15.08
1.37
14.74
1.42
15.63
1.38
15.28
1.42
16.32
1.38
15.95
1.43
16.59
1.38
16.22
1.43
16.64
1.37
16.30
1.42
16.72
1.36
16.44
1.39
16.80
1.35
16.58
1.37
16.85
1.34
16.67
1.36
16.90
1.33
16.75
1.34
TC: Total Capacity (kBtu/h)
©
PERFORMANCE DATA
Maximum Heating Capacity
Indoor Air Temp. °F DB
68
70
TC
PI
TC
PI
8.27
1.18
8.14
1.20
9.19
1.27
9.04
1.29
9.67
1.32
9.51
1.34
10.27
1.38
10.10
1.40
10.66
1.35
10.49
1.37
11.18
1.33
11.00
1.35
11.34
1.29
11.16
1.31
11.50
1.24
11.31
1.26
11.70
1.19
11.51
1.21
11.86
1.15
11.67
1.17
12.02
1.11
11.83
1.13
12.22
1.05
12.02
1.07
12.30
1.03
12.10
1.05
12.41
1.02
12.23
1.03
12.60
1.00
12.46
1.01
12.79
0.98
12.68
0.98
12.90
0.96
12.81
0.97
13.01
0.95
12.95
0.96
Capacity as rated: 0 ft. above sea level with 24.6 ft. of refrigerant piping. 0 ft. level difference between
outdoor and indoor units.
Heating capacity rating obtained with air entering the indoor unit at 70ºF dry bulb (DB) and 60ºF wet
bulb (WB), and outdoor ambient conditions of 47ºF dry bulb (DB) and 43ºF wet bulb (WB).
Indoor Air Temp. °F DB
68
70
TC
PI
TC
PI
8.22
1.24
8.08
1.26
9.44
1.33
9.28
1.35
10.08
1.38
9.91
1.40
10.88
1.45
10.70
1.47
11.40
1.45
11.21
1.47
12.10
1.45
11.90
1.47
12.62
1.45
12.41
1.47
13.14
1.45
12.93
1.48
13.80
1.46
13.57
1.48
14.32
1.46
14.09
1.49
14.84
1.47
14.60
1.49
15.50
1.47
15.24
1.50
15.76
1.47
15.50
1.50
15.90
1.46
15.67
1.48
16.14
1.43
15.96
1.44
16.38
1.40
16.24
1.41
16.52
1.38
16.41
1.39
16.67
1.36
16.58
1.36
Capacity as rated: 0 ft. above sea level with 24.6 ft. of refrigerant piping. 0 ft. level difference between
outdoor and indoor units.
Heating capacity rating obtained with air entering the indoor unit at 70ºF dry bulb (DB) and 60ºF wet
bulb (WB), and outdoor ambient conditions of 47ºF dry bulb (DB) and 43ºF wet bulb (WB).
LC098HV, LC128HV
72
75
TC
PI
TC
PI
8.03
1.22
7.74
1.26
8.92
1.31
8.59
1.34
9.38
1.36
9.04
1.40
9.97
1.42
9.60
1.46
10.35
1.39
9.97
1.43
10.85
1.37
10.46
1.41
11.01
1.32
10.61
1.36
11.16
1.28
10.76
1.32
11.36
1.23
10.94
1.26
11.51
1.18
11.09
1.22
11.67
1.14
11.24
1.17
11.86
1.09
11.43
1.12
11.94
1.06
11.51
1.10
12.09
1.05
11.68
1.08
12.34
1.02
11.97
1.04
12.59
0.99
12.27
1.01
12.74
0.97
12.44
0.99
12.89
0.96
12.62
0.97
72
75
TC
PI
TC
PI
7.97
1.28
7.68
1.32
9.16
1.37
8.82
1.41
9.78
1.42
9.42
1.47
10.56
1.49
10.17
1.53
11.07
1.49
10.66
1.53
11.74
1.49
11.31
1.53
12.25
1.49
11.80
1.54
12.76
1.50
12.29
1.54
13.39
1.50
12.90
1.55
13.90
1.51
13.39
1.55
14.41
1.51
13.88
1.56
15.04
1.52
14.49
1.56
15.29
1.52
14.74
1.57
15.49
1.50
14.96
1.54
15.81
1.46
15.34
1.49
16.13
1.42
15.72
1.44
16.32
1.39
15.94
1.41
16.52
1.37
16.17
1.38
PERFORMANCE DATA | 61