Status Texts - Deif AGC 150 Operator's Manual

Generator marine stand-alone
Hide thumbs Also See for AGC 150:
Table of Contents

Advertisement

Display text
You can select five of the display texts for each display view.
3.4

Status texts

Status text
ACCESS LOCK
Aux. test ##.#V ####s
COOLING DOWN ###s
DG BLOCKED FOR START The generator has stopped and has active alarm(s).
EDG READY AUTO
EDG READY SEMI
EDG RUNNING SEMI
EMERGENCY SUPPLY
EXT. STOP TIME ###s
FULL TEST ###.#min
GB ON BLOCKED
GB TRIP EXTERNALLY
GEN. RUNNING LOCAL
GEN. RUNNING REMOTE
GEN. SUPPLY LOCAL
GEN. SUPPLY REMOTE
GENSET READY REMOTE
GENSET READY LOCAL
GENSET STOPPING
Hz/V OK IN ###s
IDLE RUN
IDLE RUN ###.#min
ISLAND ACTIVE
Operator's manual 4189341314C EN
Condition
The configurable input is activated, and the operator tries to activate one of the blocked keys.
The battery test is activated.
Cooling-down period is activated.
The controller is in auto mode and ready to start in case of blackout.
The controller is in semi-auto mode and ready for external signals or operator input.
The genset is running in semi-auto mode. The breaker is open.
The controller is in auto mode and supplying power from the emergency generator due to
blackout on the mains busbar.
The extended stop timer is running.
Test mode is activated and test timer counting down.
The generator is running, the GB is open and there is an active Trip GB alarm.
Some external equipment has tripped the breaker. An external trip is logged in the event log.
Genset running in local mode.
Genset running in remote mode.
Genset is supplying busbar in local mode.
Genset is supplying busbar in remote mode.
The controller is in remote mode and ready to respond.
The controller is in local mode and waiting for operator input.
Cooling down has finished.
The voltage and frequency on the genset is OK. When the timer runs out the generator breaker
can be closed.
The idle run input is active.
The idle run function is active. During a start the genset will not go to nominal RPMs. During a
stop the genset will not stop before the timer has expired.
The controller is in remote mode and supplying power.