Mitsubishi Electric MXZ-4E72VA-E1 Service Manual page 7

Hide thumbs Also See for MXZ-4E72VA-E1:
Table of Contents

Advertisement

Outdoor model
Outdoor unit power supply
Indoor units number
Piping total length
Connecting pipe length
Height difference (Indoor ~ Outdoor)
Height difference (Indoor ~ Indoor)
Function
Capacity Rated frequency (Min.-Max.) 2
Breaker capacity
Power input (Total) 1, 2
Running current (Total) 1, 2
Power factor (Total) 1, 2
Starting current (Total) 1, 2
Coeffi cient of performance (C.O.P) (Total) 1, 2
Model
Output
Current 1, 2
Refrigeration oil (Model)
Model
Current 1, 2
Dimensions W x H x D
Weight
Air fl ow (Rated)
Sound level (Rated)
Fan speed (Rated)
Refrigerant fi lling capacity (R410A)
1 Measured under rated operating frequency.
2 When connected with indoor units below.
MSZ-EF18VE + MSZ-EF18VE + MSZ-EF18VE + MSZ-EF18VE
3 220 and 240 V are only -
NOTE: Test conditions are based on ISO 5151. (Refrigerant piping length (one way): 5 m)
COOLING INDOOR
Dry-bulb temperature 27.0 °C Wet-bulb temperature 19.0 °C
OUTDOOR Dry-bulb temperature 35.0 °C Wet-bulb temperature 24.0 °C
HEATING INDOOR
Dry-bulb temperature 20.0 °C
OUTDOOR Dry-bulb temperature 7.0 °C Wet-bulb temperature 6.0 °C
OBH723G
m
m
m
m
kW
A
W
A
%
A
W
A
L
A
mm
kg
3
m
/h
dB(A)
rpm
kg
E2
,
ET2
and -
ER2
.
MXZ-4E72VA
Single phase
220 -230 - 240 V, 50 Hz / 220V, 60Hz 3
2 to 4
Max. 60
Max. 25
Refer to 7 REFRIGERANT SYSTEM DIAGRAM.
Refer to 7 REFRIGERANT SYSTEM DIAGRAM.
Cooling
7.2 (3.7 - 8.8)
2,250
10.3 - 9.9 - 9.5
10.0
3.20
SNB172FEGH1T
2,000
9.46
0.7 (NEO22)
,
,
: SIC-71FW-F764-2
ET1
ER1
E1
,
,
: SIC-82FX-F764-1
ET2
ER2
E2
0.2
840 x 710 x 330
2,334
50
650
2.7
7
Heating
8.6 (3.4 - 10.7)
25
2,280
10.5 - 10.0 - 9.6
99
3.77
9.56
59
2,376
53
660

Hide quick links: