Affix Cabinets To Floor - Trane VFDB Installation, Operation And Maintenance Manual

Remote-mounted medium voltage air-cooled adaptive frequency drive with tracer adaptiview control
Table of Contents

Advertisement

Figure 28. Secure the cabinets, B-frame
2-socket screw M6x16
Combination pillar

Affix Cabinets to Floor

WARNING
Drive Mounting Instructions!
Failure to correctly anchor the cabinet could result in
death or serious injury and equipment damage. Refer to
Rockwell's technical drawings and installation manual
for drive mounting instructions. Contact the area
Rockwell Automation sales office if you do not have
these documents.
Typical floor drawings show minimum clearance distance,
conduit openings, and mounting holes for anchor bolts, as
shown in below
Figure 6, p.
p.
28.
Secure the cabinet to the channel steel base using M12 bolt
(recommended), lock washer, two flat washers, and a nut as
shown in
Figure
29.
VFDB-SVX001C-EN
21,
Figure 7, p. 22
and
Figure 13,
Secure with M6
hardware (8 places)
Figure 29. Bolt cabinet to steel base, B-frame
Lock washer
Flat washer
Optional: The cabinet can also be welded to the steel base
once it is securely bolted, if desired.
Each weld location should be 3.9 in. (100 mm) for every 39.4
in. (1000 mm). See Mounting Requirements in the PowerFlex
6000T Drives Shipping and Handling Manual, publication
6000-PC100 for further information on the steel base and
desired trench and mounting customer-specifications.
Mechanical Installation
M16 bolt
37