Indoor Fan Control - Fujitsu AOYR14LCL Service Instruction

Wall mounted type inverter, refrigerant r410a, indoor/outdoor unit
Table of Contents

Advertisement

5. INDOOR FAN CONTROL

(1).Fan speed
( Table 5 : Indoor Fan Speed )
Operat ion mode
Heating
Cooling
Fan
Dry
Operation mode
Heating
Cooling
Fan
Dry
(2).FAN OPERATION
The airflow can be switched in 5 steps such as AUTO, QUIET, LOW, MED, HIGH, while the indoor
fan only runs.
When Fan mode is set at (Auto), it operates on (MED) Fan Speed.
07/09LCC, 09LDC
Air flow mode
Speed (rpm)
Hi
Me+
Me
Lo
Quiet
Cool air
prevention
S-Lo
Hi
Me
Lo
Quiet
14/18LCC
Air flow mode
Speed (rpm)
Hi
Me+
Me
Lo
Quiet
Cool air
prevention
S-Lo
Hi
Me
Lo
Quiet
Operation mode
1390
Heating
1350
1200
1000
760
760
480
1300
Cooling
1120
Fan
950
700
700
Dry
1480
1420
1300
1110
950
850
480
1480
1260
1040
850
850
05-05
12LCC, 12LDC
Air flow mode
Speed (rpm)
Hi
1440
Me+
1350
Me
1200
Lo
1000
Quiet
760
Cool air
760
prevention
S-Lo
480
Hi
1370
Me
1150
Lo
950
Quiet
700
700

Hide quick links: