Fujitsu AOYR14LCL Service Instruction page 61

Wall mounted type inverter, refrigerant r410a, indoor/outdoor unit
Table of Contents

Advertisement

JP (Jumper) Setting
[Indoor Unit]
ASYA07/09/12LCC
ASYB09/12LDC
ASYA14/18LCC
- Remote control custom code
When multiple number of indoor units are installed in the same room, erroneous receipt of the signal can
be avoided by setting up the remote control custom code separately.
To set up the remote control custom code, always set up the same code on both indoor unit PCB and
remote control PCB.
(When the indoor unit PCB is changed to Code B, it can not receive the signal unless remote control PCB
is also changed to Code B.)
Code A (Default)
Code B
- Auto Restart
It is possible to disengage Auto Restart function if it is not needed.
With Auto Restart function
(Default)
Without
Auto
Restart
function
[Outdoor Unit]
AOYR07/09/12LCC
07/09LCC
Normal Preheat
Higher Preheat
12LCC
Normal Preheat
Higher Preheat
AOYS09/12LDC
09LDC
Normal Preheat
Higher Preheat
12LDC
Normal Preheat
Higher Preheat
AOYR14/18LCC
14LCC
Normal Preheat
Higher Preheat
18LCC
Normal Preheat
Higher Preheat
- it is possible to select the higher or standard level of preheating function.
- When it is set up at the higher level of preheat, the magnetic noise of the compressor becomes higher.
Indoor Unit
Remote Control
JM1(JP)
Indoor Unit
JM2 (JP)
JP
JM500
JM103
JM102
JP
JM500
JM103
JM102
JP
JM500
JM103
JM102
08-01
J4 (JP)
JM101
JM101
JM101