3-2. Outdoor fan control

¢ Outdoor fan motor
This outdoor unit has a DC fan motor. (Control method is different between AC and DC motors.)
¢ Fan speed
 Model: AOYG18KATA
Fan speed is defined by outdoor temperature and compressor frequency.
• Outside air temperature zone selection
Cooling
Fan step
Y zone
S-HIGH2
S-HIGH1
HIGH
10
9
8
7
6
5
4
3
2
1
NOTE: After defrost control on the heating mode, the fan speed is kept higher regardless of the
compressor frequency.
Fan speed after defrost control: 1,120 rpm
3-2. Outdoor fan control
Outside air
temperature rises
21°C
12°C
2°C
-8°C
Heating
Y zone
1,120
990
1,120
990
1,120
1,120
990
1,120
990
950
890
830
830
750
780
710
780
660
670
500
570
500
520
500
Outside air
temperature drops
Y zone
Z zone
F zone
G zone
H zone
Dry
Cooling or dry at low outdoor temp.
Z zone
F zone
990
630
990
630
890
630
830
400
780
400
780
400
670
310
570
200
520
200
- (04-12) -
19°C
10°C
0°C
-10°C
Unit: rpm
G zone
360
300
360
300
360
300
300
280
270
230
240
200
220
200
220
200
200
200
H zone
300
300
300
280
230
200
200
200
200
3. Fan control