Fujitsu AO G18KATA Series Service Instruction page 18

Cassette type inverter
Hide thumbs Also See for AO G18KATA Series:
Table of Contents

Advertisement

 Model: AOYG22KATA
Fan speed is defined by outdoor temperature and compressor frequency.
• Outside air temperature zone selection
Cooling
Fan step
Y zone
S-HIGH2
S-HIGH1
1,050
HIGH
1,050
10
9
1,050
8
1,050
7
6
5
4
3
2
1
NOTE: After defrost control on the heating mode, the fan speed is kept higher regardless of the
compressor frequency.
Fan speed after defrost control: 1,100 rpm
3-2. Outdoor fan control
Outside air
temperature rises
21°C
12°C
2°C
-8°C
Heating
Y zone
1,100
1,100
1,100
1,100
1,100
900
900
710
900
570
770
510
630
470
510
420
400
420
400
420
Outside air
temperature drops
Y zone
Z zone
F zone
G zone
H zone
Dry
Cooling or dry at low outdoor temp.
Z zone
1,050
850
1,050
850
900
770
900
630
770
440
630
320
510
320
400
320
400
320
- (04-13) -
19°C
10°C
0°C
-10°C
F zone
G zone
340
270
340
270
340
270
270
230
270
230
270
230
270
230
270
230
270
230
Unit: rpm
H zone
270
270
270
230
230
230
230
230
230