6) Don't forcibly stretch the pipe joint, otherwise indoor capillary or other pipes might be damaged and
lead to refrigerant leakage.
4.4.2 Manifold
(1) Y-type manifold, T-type manifold.
(2) Y-type manifold has several pipe sections with different pipe size, which facilitates to match with
various copper pipe. Use pipe cutter to cut in the middle of the pipe section with different pipe size and
deburr as well. Y-type manifold must be installed vertically or horizontally.
Fig.23 (a) Y-type manifold
Fig.23 (b) T-type manifold
Fig.24 (a)