2) Space dimension for dual-module unit
3.2.2 Space requirement for the top of outdoor unit
When there is wall (or similar obstruction) above the unit, keep the distance between the unit top and the
wall at least 3000mm (118-1/8in.) or above. When the unit is located in a totally open space with no
obstructions in four directions, keep the distance between the unit top and wall at least 1500mm (59in.) or
above. When space is limited within 1500mm (59in.) or the unit is not set in an open space, air outlet pipe
is required to be installed in order to keep good ventilation.
Fig.3
Fig.4
6
Ultra Heat GMV Multi VRF