4.3.5.4 For multi-module system, select appropriate branch ("M1, M2") connected to outdoor module as
per the pipe size of basic outdoor module.
Pipe between module and outdoor branch "M1, M2":
Basic module
GMV-V72W/A-F(U)
GMV-V96W/A-F(U)
Selection of branch "Y1" of outdoor modules:
Module's capacity (C) (Btu/h)
4.3.5.5 Branch selection of the indoor unit side ("A1, A2, A3")
Manifold at indoor unit side can be selected as per total capacity of downstream indoor unit(s).
Please refer to the following table.
R410A refrigerant system
Y-type Branch Pipe
T-type Branch Pipe
4.3.5.6 Piping size among upstream branches ("b, e")
Total rated capacity of downstream
indoor units: X(Btu/h)
X≤17100
17100<X≤48500
48500<X≤72000
72000<X≤96000
96000<X≤144000
144000<X≤216000
216000<X≤240000
240000<X≤336000
Gas pipe mm(inch)
C≥144000
Total Capacity of the Downstream Indoor Unit X(Btu/h)
Φ34.9(1-3/8)
Φ34.9(1-3/8)
Φ34.9(1-3/8)
Pipe between outdoor unit and the first indoor branch
Φ28.6(1-1/8)
Φ28.6(1-1/8)
C≤68000
68000<C≤102000
102000<C≤239000
239000<C
C≤136000
136000<C≤232000
232000<C
Size of connection pipe between branches
Gas pipe mm(inch)
Φ12.7(1/2)
Φ15.9(5/8)
Φ19.05(3/4)
Φ22.2(7/8)
Φ28.6(1-1/8)
Φ34.9(1-3/8)
Φ34.9(1-3/8)
Φ34.9(1-3/8)
19
Φ15.9(5/8)
Φ15.9(5/8)
Φ15.9(5/8)
Liquid pipe mm(inch)
Φ12.7(1/2)
Φ12.7(1/2)
Model
ML01/A
Model
FQ01A/A
FQ02/A
FQ03/A
FQ03/A
FQ014/H1
FQ018/H1
FQ018/H2
Liquid pipe mm(inch)
Φ6.35(1/4)
Φ9.52(3/8)
Φ9.52(3/8)
Φ9.52(3/8)
Φ12.7(1/2)
Φ15.9(5/8)
Φ15.9(5/8)
Φ19.05(3/4)