Gree GMV-V72W/A-F Owner's Manual page 20

Hide thumbs Also See for GMV-V72W/A-F:
Table of Contents

Advertisement

between outdoor
Outdoor unit at lower(2)
unit and indoor unit
Height difference between indoor units
Maximum length of Main pipe(3)
From IDU to its nearest branch (4)
Notices:
(1) Normally, the pipe length from the first branch of IDU to the farthest IDU is 40m (131-1/4feet).
Under the following conditions, the length can reach 90m (295-1/4feet).
1) Actual length of pipe in total: L1+L2 × 2+L3 × 2+L4 × 2+...+L9 × 2+a+b+...+i+j≤1000m (3280-
3/4feet).
2) Length between each IDU and its nearest branch a, b, c, d, e, f, g, h, i, j≤40m (131- 1/4feet).
3) Difference between the pipe length from the first branch of IDU to the farthest IDU and the pipe
length from the first branch of IDU to the nearest IDU: L10-L11≤40m (131-1/4feet).
(2) When the outdoor unit is at upper side and height difference is more than 50m, please consult
company for the related technical requirement.
(3) When the maximum length of the main pipe from ODU to the first branch of IDU is ≥50m (164ft),
then adjust the pipe size.
Total rated capacity of ODU: C
(Btu/h)
GMV-V72W/A-F(U)
GMV-V96W/A-F(U)
GMV-V144WM/A-F(U)
GMV-V168WM/A-F(U)
GMV-V192WM/A-F(U)
(4) If the length between an IDU and its nearest branch is above 10m (32-4/5feet), then increase the
size of the liquid pipe of IDU (only for the pipe size that is≤6.35mm (1/4inch).
4.3.4 Connection pipe among outdoor modules
≤40(131-1/4)
≤15(49)
≤90(295-1/4)
≤40(131-1/4)
Pipe between outdoor unit and the first indoor branch
Gas pipe mm(inch)
No need to enlarge pipe size
No need to enlarge pipe size
No need to enlarge pipe size
No need to enlarge pipe size
No need to enlarge pipe size
16
Ultra Heat GMV Multi VRF
——
——
L1
a, b, c, d, e, f, g, h, i, j
Liquid pipe mm(inch)
No need to enlarge pipe size
No need to enlarge pipe size
Φ19.05(3/4)
Φ19.05(3/4)
Φ19.05(3/4)