TPM 155/22

Statement of installations

Installation
Shaft from concrete or aerated concrete
Shaft from fire-resistant panels
– specific weight min 500 kg/m
– shaft wall thickness min. 30 mm while
respecting shaft wall thickness in accordance
with the given duct fire resistance class* for
the given pressure; e.g.:
• 50 mm PROMATECT L 500
• 45 mm THERMAX SL (Tecniver)
• 45 mm GEOTEC S
• 45 mm GEOFLAM F
• 35 mm GEOFLAM F Light
Shaft from fire-resistant panels
– specific weight min 500 kg/m
– shaft wall thickness min. 30 mm while
respecting shaft wall thickness in accordance
with the given duct fire resistance class* for
the given pressure; e.g.:
• 40 mm PROMATECT L 500
• 45 mm THERMAX SL (Tecniver)
• 45 mm GEOTEC S
• 35 mm GEOFLAM F
• 35 mm GEOFLAM F Light
Shaft from fire-resistant panels
– specific weight min 500 kg/m
– shaft wall thickness min. 30 mm while
respecting shaft wall thickness in accordance
with the given duct fire resistance class* for
the given pressure; e.g.:
• 30 mm PROMATECT L 500
• 45 mm THERMAX SL (Tecniver)
• 30 mm GEOTEC S
• 30 mm GEOFLAM F
• 35 mm GEOFLAM F Light
Shaft from fire-resistant panels
– specific weight min 500 kg/m
– shaft wall thickness min. 30 mm while
respecting shaft wall thickness in accordance
with the given duct fire resistance class* for
the given pressure; e.g.:
• 35 mm THERMAX SL (Tecniver)
* Duct system must be tested and classified in accordance with EN 13501-4
Version 2023-06-07
shaft wall
Filling the gap
min. thickness
between the damper
[mm]
and a shaft wall
Mortar or gypsum
Mastic
70
Installation frame -
mortar or gypsum
Installation frame -
mastic
Mortar or gypsum
Mastic
Installation frame -
mortar or gypsum
Installation frame -
mastic
Mortar or gypsum
Mastic
Installation frame -
mortar or gypsum
Installation frame -
mastic
Mortar or gypsum
Mastic
Installation frame -
mortar or gypsum
Installation frame -
mastic
Mortar or gypsum
Mastic
Installation frame -
mortar or gypsum
Installation frame -
mastic
Smoke extraction damper - SEDM-D
Fire resistance
EI 120 (v
i
o)S1500C
AAmulti
ed
300
EI 120 (v
i
o) S1500C
AAmulti
ed
300
EI 90 (v
i
o) S1500C
AAmulti
ed
300
EI 60 (v
i
o) S1500C
AAmulti
ed
300
EI 60 (v
i
o) S500C
AAmulti
ed
300
Page
25
25
26
26
27
27
28
28
27
27
28
28
27
27
28
28
27
27
28
28