Installation - Shaft From Concrete Or Aerated Concrete - Mandik SEDM-D Installation, Operation, Maintenance And Service Manual

Smoke extraction damper-multi
Table of Contents

Advertisement

TPM 155/22

Installation - shaft from concrete or aerated concrete

With mastic, mortar or gypsum
Installation opening
B + 10
1 Concrete or aerated concrete
2 Fire-resistant mastic (E.g. HILTI Firestop Acrylic coating SFS-S ACR),
mortar or gypsum
3 SEDM-D
4 Screw 6x100 mm 4x (connection of the damper with shaft)
Version 2023-06-07
≥ 70
A
Smoke extraction damper - SEDM-D
≥ 70
Detail A
Detail of connection of the damper with shaft
Page 25