Electric Parameters, Wiring Diagram - Mandik SEDM-D Installation, Operation, Maintenance And Service Manual

Smoke extraction damper-multi
Table of Contents

Advertisement

TPM 155/22

Electric parameters, wiring diagram

Degree of protection (electric part)
Maximum connecting wire cross-section (terminal block size)
Temperature range
Design variant
Activation signal
Nominal voltage
Voltage range
Input power
Resistance
Inductance
Length of activation pulse
Temperature validation test
Continuous operation test at 20°C
Compliance
Type; configuration
Voltage
Switchable DC current
Contact resistance
Insulation voltage open contact
Cut-off power (DC)
Longevity – cycles
Microswitch AC rating
Microswitch degree of protection
Compliance
Nominal voltage
Voltage range
Power input
Dimensioning
Recommended switch-on time
Rearming time at room temperature
Longevity – cycles
Cycling period
Maintenance
Compliance
Version 2023-06-07
SEDM-D damper assembly
Restraint mechanism (magnet)
24
voltage pulse [émission du curent]
24 V DC
20.4 ... 28.8 V
3.5 W
173 Ohm ± 5%
0.19 H ± 5%
End-switches
Rearming motor
Smoke extraction damper - SEDM-D
-25 ... 50 °C
≥ 1 s
70 °C for 1 hour
> 5 hours
NF 61.937-1, NF 61.937-10
G905; (C-NO-NC)
≤ 60 V DC
> 0.5 A
< 0.1 Ohm
> 500 V
> 10 W
> 1000
230 V AC / 5 A
IP67
NF 61.937-1, NF 61.937-10
24 V / 48 V DC
20.4 ... 57.6 V
20 W
29 VA
40 s
< 30 s
≥ 300
min. 120 s
maintenance free
NF 61.937-1, NF 61.937-10
IP42
2
2.5 mm
48
48 V DC
40.8 ... 57.6 V
3.5 W
695 Ohm ± 5%
0.71 H ± 5%