Summary of Contents for Mandik SEDM-D

  • Page 1 TPM 155/22 Version 2023-06-07 SEDM-D Smoke extraction damper-multi Technical Documentation Installation, Commissioning, Operation, Maintenance and Service Manual www.mandik.com MANDÍK, a. s. • Dobříšská 550 • 267 24 Hostomice • Czech Republic • Tel.: +420 311 706 742 • E-Mail: mandik@mandik.cz...
  • Page 2: Table Of Contents

    TPM 155/22 These technical specifications state a typerange of manufactured sizes and models of smoke extraction dampers SEDM-D It is valid for production, designing, ordering, delivery, maintenance and operation. CONTENT I. GENERAL.....................................3 Description....................................3 II. DESIGN.......................................5 Hand-operated designs................................6 Rearming motor designs.................................6 Grilles designs..................................9...
  • Page 3: General

    SEDM-D The dampers may be installed to the shaft directly using dampers open to the inside of the duct. The dampers opened...
  • Page 4 Certificate of Constancy of Performance No. 1391-CPR-2023/0030 ■ Declaration of Performance No. PM/SEDM-D/01/23/1 ■ EU Declaration of Conformity No. PM/SEDM-D/03/23/2 ■ Efectis France Test report on fitness for use of mechanisms No. EFR-22-0000822 ■ In accordance with NF 61.937-1 and NF 61.937-10 ■...
  • Page 5: Design

    The damper is equipped with a restraint mechanism keeping (security) to the position closed (stand-by). the damper closed. The restraint mechanism includes a permanent magnet combined with an electric coil with SEDM-D hand-operated design SEDM-D rearming motor design Version 2023-06-07 Smoke extraction damper - SEDM-D Page 5...
  • Page 6: Hand-Operated Designs

    48 V DC and with two pairs of end switches signaling of 48 V DC, with two pairs of end switches signaling of the the damper blade position "CLOSED" (STAND-BY) and damper blade position "CLOSED" (STAND-BY) and "OPEN" "OPEN" (SECURITY). (SECURITY). Page 6 Smoke extraction damper - SEDM-D Version 2023-06-07...
  • Page 7 > 500 V Cut-off power (DC) > 10 W Longevity – cycles > 1000 Microswitch AC rating 230 V AC / 5 A Microswitch degree of protection IP67 Compliance NF 61.937-1, NF 61.937-10 Version 2023-06-07 Smoke extraction damper - SEDM-D Page 7...
  • Page 8 Recommended switch-on time 40 s Rearming time at room temperature < 30 s Longevity – cycles ≥ 300 Cycling period min. 120 s Maintenance maintenance free Compliance NF 61.937-1, NF 61.937-10 Page 8 Smoke extraction damper - SEDM-D Version 2023-06-07...
  • Page 9: Grilles Designs

    Simple, the lightest grille made from a punched 2 mm Al sheet, 77% effective area. ■ 12 mm Grille G2 Design grille with aerodynamic profile louvers made from Al alloy, 77% effective area. ■ 26 mm (from the wall) Version 2023-06-07 Smoke extraction damper - SEDM-D Page 9...
  • Page 10 M5 screws (Detail B - 4x M5 screw, 4x M5 nut and 8x washer), then secure the grille with two M4 screws. Grille G4 Design grille made of steel (punched and drawn), 78% effective area. ■ 12 mm Page 10 Smoke extraction damper - SEDM-D Version 2023-06-07...
  • Page 11: Electric Parameters, Wiring Diagram

    Recommended switch-on time 40 s Rearming time at room temperature < 30 s Longevity – cycles ≥ 300 Cycling period min. 120 s Maintenance maintenance free Compliance NF 61.937-1, NF 61.937-10 Version 2023-06-07 Smoke extraction damper - SEDM-D Page 11...
  • Page 12 End-switch position closed – normally contact violet FCB O1 (C) End-switch position open – input yellow FCB O2 (NO) End-switch position open – normally open green FCB O3 (NC) End-switch position open – normally contact Page 12 Smoke extraction damper - SEDM-D Version 2023-06-07...
  • Page 13: Damper Control

    Rearming should be carried out with the smoke extraction fan off for safety of persons and equipment. Security position (damper is open) Stand-by mode (damper is closed) Restraint mechanism Version 2023-06-07 Smoke extraction damper - SEDM-D Page 13...
  • Page 14 Making sure that the damper is well secured by an Stand-by mode (damper is closed) attempt to open the damper by pushing the blade Installing or closing and securing the protection grille Security position (damper is open) Page 14 Smoke extraction damper - SEDM-D Version 2023-06-07...
  • Page 15: Dimensions

    M5 *For the side H ≤ 600 mm, there are only two cage nuts on this side. For the side B, there is always one B + 39 cage nut. Version 2023-06-07 Smoke extraction damper - SEDM-D Page 15...
  • Page 16: Technical Parameters

    Designs with rearming motor can be manufactured from 350 x 385 mm. ** For designs with rearming motor a weight of 1,4 kg must be added. For designs with end switch module a weight of 0,17 kg must be added. Page 16 Smoke extraction damper - SEDM-D Version 2023-06-07...
  • Page 17 Designs with rearming motor can be manufactured from 350 x 385 mm. ** For designs with rearming motor a weight of 1,4 kg must be added. For designs with end switch module a weight of 0,17 kg must be added. Version 2023-06-07 Smoke extraction damper - SEDM-D Page 17...
  • Page 18: Installation

    Minimum distance between dampers and the construction minimum distance 200 mm between dampers, according to EN 1366-10 ■ minimum distance 75 mm between the damper and the construction, according to EN 1366-10 ■ ≥ 75 ≥ 200 Page 18 Smoke extraction damper - SEDM-D Version 2023-06-07...
  • Page 19: Statement Of Installations

    Installation frame - • 35 mm THERMAX SL (Tecniver) mastic * Duct system must be tested and classified in accordance with EN 13501-4 Version 2023-06-07 Smoke extraction damper - SEDM-D Page 19...
  • Page 20: Installation Procedure

    Check that all cage nuts or other elements necessary for the connection of the grille are on the damper. Fill the inside of the damper frame with mastic, mortar or gypsum. Install SEDM-D into the centre of installation opening using wedges or spacers. Pull the connecting cable including a special grommet through the wall.
  • Page 21: Cable Connection

    Seal the cable passage through the shaft wall and through the damper casing. Grommet Cable behind the lever Cable in front of the lever Anti-traction clip Version 2023-06-07 Smoke extraction damper - SEDM-D Page 21...
  • Page 22: Shock Absorber

    Use a shock absorber that is delivered with the damper (attach it to the shaft wall or damper blade) to prevent damage of ■ SEDM-D. Height of the shock absorber depends on the distance of the damper from the shaft wall. Shaft from fire-resistant panels...
  • Page 23 4) After hardening the mastic, mortar or gypsum you can remove frame reinforcements by unscrewing the screws and after that, bend or snap mouting plates for frame reinforcements. Bend or snap Version 2023-06-07 Smoke extraction damper - SEDM-D Page 23...
  • Page 24 TPM 155/22 5) Prepare SEDM-D and set four fastening plates to the "open" position. 6) Install SEDM-D on the frame and mount it on four fastening plates. Page 24 Smoke extraction damper - SEDM-D Version 2023-06-07...
  • Page 25: Installation - Shaft From Concrete Or Aerated Concrete

    1 Concrete or aerated concrete 2 Fire-resistant mastic (E.g. HILTI Firestop Acrylic coating SFS-S ACR), mortar or gypsum 3 SEDM-D 4 Screw 6x100 mm 4x (connection of the damper with shaft) Version 2023-06-07 Smoke extraction damper - SEDM-D Page 25...
  • Page 26 Concrete or aerated concrete Fire-resistant mastic (E.g. HILTI Firestop Acrylic coating SFS-S ACR), mortar or gypsum SEDM-D → see page 23 Installation frame installation procedure Installation frame and damper fastening plate 4x Page 26 Smoke extraction damper - SEDM-D Version 2023-06-07...
  • Page 27: Installation - Shaft From Fire-Resistant Panels

    * X = shaft wall thickness in accordance with the given duct Screw 5x70 mm 4x (connection of the damper with shaft) → see page 19 fire resistance class for the given pressure Version 2023-06-07 Smoke extraction damper - SEDM-D Page 27...
  • Page 28 Installation frame - installation procedure * X = shaft wall thickness in accordance with the given duct Installation frame and damper fastening plate 4x → see page 19 fire resistance class for the given pressure Page 28 Smoke extraction damper - SEDM-D Version 2023-06-07...
  • Page 29: Technical Data

    0,333 1000 0,963 0,786 0,659 0,565 0,492 0,434 0,387 0,348 0,316 1050 0,930 0,760 0,637 0,546 0,475 0,419 0,374 0,337 0,305 1100 0,916 0,748 0,628 0,537 0,468 0,413 0,368 0,331 0,301 Version 2023-06-07 Smoke extraction damper - SEDM-D Page 29...
  • Page 30: Material, Finishing

    The warranty for fire dampers SEDM-D, provided by the ■ are mechanically damaged during handling. manufacturer, is completely void if closing and control...
  • Page 31: Assembly, Attendance And Maintenance

    Data label is placed on the damper casing (example) MANDÍK, a.s. Dobříšská 550, 267 24 Hostomice, Czech Republic DIMENSION: DESIGN: WEIGHT (kg): SERIAL.NO.: MANUAL CLASSIFICATION: Cert. No.: 1391-CPR-XXXX/XXXX, DoP: PM/XXXX/XX/XX/X TPM XXX/XX EN 12101-8 Version 2023-06-07 Smoke extraction damper - SEDM-D Page 31...
  • Page 32: Ordering Key

    TPM 155/22 Ordering key Smoke extraction dampers SEDM-D SEDM-D 700x1100 .24C0H F / G1 / RAL 9010 — - without paint - for grille G1 only* grille colour* G1 - simple grille with punched profiles G2 - design grille with aerodynamic profiles...
  • Page 33: Accessories

    TPM 155/22 Accessories Grille G1 SEDM-D 300x300 RAL 9010 Grille colour RAL Size B (width) x H (height) Grille type G1 - simple grille with punched profiles G2 - design grille with aerodynamic profiles G3 - design grille with thin louvers with hidden bolts...
  • Page 34 The producer reserves the right for innovations of the product. For actual product information see www.mandik.com www.mandik.com MANDÍK, a. s. • Dobříšská 550 • 267 24 Hostomice • Czech Republic • Tel.: +420 311 706 742 • E-Mail: mandik@mandik.cz...