Individual settings
6.2

Settings on the Bosch Heatronic

6.2.1

Operating the Bosch Heatronic

The Bosch Heatronic enables easy setting and check-
ing of a large number of appliance functions.
This description is limited to those functions required
for commissioning.
For a full description of all available functions, please
refer to the Service booklet for the Engineer, order no.
7-181-465-348.
5
2
1
6 720 610 332-30.1O
3
4
Fig. 37 Appliance controls
1
Service button
2
"Chimney sweep" button
3
Temperature control for central heating
4
Temperature control for hot water
5
Display
Selecting service function:
Note the positions of the temperature con-
i
trols
and
tings, return the temperature controls to
their original positions.
The service functions are subdivided into two levels:
Level 1 comprises service functions up to function 4.9,
while Level 2 consists of the service functions from 5.0
upwards.
B To select a service function on Level 1: press and
hold the
button until the display shows – –.
B To select a service function on Level 2: press and
hold the buttons
and
display shows = =.
B Then turn the
temperature control to select the
required function.
Service function
Anti-cycle time
Max. CH flow
temperature
Switching difference
Max. heating output
Constant hot water
cycle time
Table 14
The service function 5.0 may be reset.
28
. After completing the set-
simultaneously until the
Code no.
See page
2.4
28
2.5
28
28
2.6
5.0
28
6.8
29
Entering a setting
B To enter the setting for a function, turn the tempera-
ture control
.
Storing a setting
B Level 1: press and hold the
play shows [ ].
B Level 2: press and hold the
taneously until the display shows [ ].
After completing the settings
B Reset the temperature controls
original positions.
6.2.2
Setting the anti-cycle time
(Service Function 2.4)
This service function is only active if Service Function
2.7, automatic anti-cycle time, is deactivated.
The anti-cycle time can be set to between 0 and 15 min-
utes (factory setting is 3 minutes).
If the setting 0 is entered, the anti-cycle time is inactive.
The shortest possible anti-cycle time is 1 minute (rec-
ommended for single-pipe and hot-air heating systems).
If the appliance is connected to an outside
i
temperature controlled heating program-
mer, the anti-cycle time does not need to
be set on the appliance and is optimised
by the programmer instead.
6.2.3
Setting the maximum CH flow tempera-
ture (Service Function 2.5)
The maximum CH flow temperature can be set to
between 35°C and 88°C (factory setting).
6.2.4
Setting the switching difference
(Service Function 2.6)
If the appliance is connected to an outside
i
temperature controlled programmer, the
programmer sets the switching difference.
It does not need to be set on the appli-
ance.
The switching difference is the permissible divergence
from the specified CH flow temperature. It can be set in
increments of 1°C. The adjustment range is 1 to 30°C
(is factory set to 0°C). The minimum CH flow temper-
ature is 30°C.
6.2.5
Setting the heating output
(Service Function 5.0)
The heating output can be set to any level between min.
rated heat output and max rated heat output to limit it to
the specific heat requirements.
The factory setting is the max. rated heat output.
button until the dis-
and
buttons simul-
and
to their
6 720 611 441 GB (03.11)