To Check The Minimum Flow Rate; Air Purge Function - Daikin Altherma EHVH08SU18CB6W Installer's Reference Manual

Low temperature split
Hide thumbs Also See for Altherma EHVH08SU18CB6W:
Table of Contents

Advertisement

To perform a test run.
To perform an actuator test run.
Underfloor screed dryout function
The underfloor screed dryout function is started (if
necessary).
9.4.1

To check the minimum flow rate

1 Confirm according to the hydraulic configuration which space
heating loops can be closed due to mechanical, electronic, or
other valves.
2 Close all space heating loops that can be closed (see previous
step).
3 Start the pump test run operation (see
actuator test run" on
page 76).
4 Go to [6.1.8]:
> Information > Sensor information > Flow rate
to check the flow rate. During pump test run operation, the unit
can operate below this minimum required flow rate.
Bypass valve foreseen?
Yes
Modify the bypass valve setting
to reach the minimum required
flow rate + 2 l/min
Minimum required flow rate
04+08 models
11+16 models
9.4.2

Air purge function

When commissioning and installing the unit, it is very important to
remove all air in the water circuit. When the air purge function is
running, the pump operates without actual operation of the unit and
the removal of air in the water circuit will start.
NOTICE
Before starting the air purge, open the safety valve and
check if the circuit is sufficiently filled with water. Only if
water escapes the valve after opening it, you can start the
air purge procedure.
There are 2 modes for purging air:
▪ Manual: the unit operates with a fixed pump speed and in a fixed
or custom position of the 3-way valve. The custom position of the
3-way valve is a more than helpful feature to remove all air from
the water circuit in the space heating or the domestic hot water
heating mode. Air purge must be performed for both the space
heating and the domestic hot water circuit. The operation speed of
the pump (slow or quick) can also be set.
▪ Automatic: the unit automatically changes the pump speed and
switches the position of the 3-way valve between the space
heating and the domestic hot water heating mode.
Typical workflow
Purging the air from the system should consist of:
1
Performing a manual air purge
2
Performing an automatic air purge
ERLQ004~008CA + EHVH04+08SU18+26CB6W
Daikin Altherma – Low temperature split
4P449978-1B – 2018.07
"9.4.4  To perform an
No
In case the actual flow rate is
below the minimum flow rate,
modifications at the hydraulic
configuration are required.
Increase the space heating loops
that can NOT be closed or install
a pressure‑controlled bypass
valve.
12 l/min
15 l/min
INFORMATION
Start by performing a manual air purge. When almost all
the air is removed, perform an automatic air purge. If
necessary, repeat performing the automatic air purge until
you are sure that all air is removed from the system.
During air purge function, pump speed limitation [9‑0D] is
NOT applicable.
Make sure that the leaving water temperature home page, room
temperature home page, and domestic hot water home page are
turned OFF.
The air purge function automatically stops after 30 minutes.
To perform a manual air purge
Prerequisite: Make sure that the leaving water temperature home
page, room temperature home page, and domestic hot water home
page are turned OFF.
1 Set the user permission level to Installer. See
permission level to Installer" on
2 Set the air purge mode: go to [A.7.3.1]
Commissioning > Air purge > Type.
3 Select Manual and press
4 Go to [A.7.3.4]
> Installer settings > Commissioning > Air
purge > Start air purge and press
function.
Result: The manual air purge starts and the following screen
appears.
Tue
Air purge
Flow rate
0.5
l/min
Speed
Low
Circuit
SHC
Scroll
Stop
Adjust
5 Use the and buttons to scroll to Speed.
6 Use the
and
buttons to set the desired pump speed.
Result: Low
Result: High
7 If applicable, set the desired position of the 3-way valve (space
heating/domestic hot water). Use the and buttons to scroll to
Circuit.
8 Use the
and
buttons to set the desired position of the 3-way
valve.
Result: SHC or Tank
To perform an automatic air purge
Prerequisite: Make sure that the leaving water temperature home
page, room temperature home page, and domestic hot water home
page are turned OFF.
1 Set the user permission level to Installer. See
permission level to Installer" on
2 Set the air purge mode: go to [A.7.3.1]
Commissioning > Air purge > Type.
3 Select Automatic and press
4 Go to [A.7.3.4]
> Installer settings > Commissioning > Air
purge > Start air purge and press
function.
Result: Air purging will start and the following screen will be
shown.
9 Commissioning
"To set the user
page 49.
> Installer settings >
.
to start the air purge
01:18
"To set the user
page 49.
> Installer settings >
.
to start the air purge
Installer reference guide
75